Electrical Connection - Riello GS10/M Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

4.2 ELECTRICAL CONNECTION,

WARNING
If the boiler has a the 7 pin plug, it should be replaced with the one supplied with the burner.
WITHOUT REGULATOR
PS
– Remote manual reset
MB
– Burner terminal block
X7
– 7 pin plug
X4
– 4 pin plug
X6
– 6 pin plug
h2
– 2nd stage hour-counter
TR
– High-low mode control
device system
h1
– 1st stage hour-counter
S
– Remote lock-out signal
IN
– Manual burner stop switch
TL
– Limit control device system
ATTENTION
Do not connect any contact
between T6 and T8 at the
4 pin plug and between T1
and T2 at the 7 pin plug, in
order to avoid interference
with the regulator.
PS – Remote manual reset
MB – Burner terminal block
X4 – 4 pin plug
20013756
(as set up by the installer)
WITH REGULATOR
X7 – 7 pin plug
BT – Temperature probe
BP – Pressure probe
(high-low progressive mode operation)
T6A – Fuse
TS
– Safety control device system
PG
– Min. gas pressure switch
VR
– Adjustment valve
VS
– Safety valve
(fully modulating mode operation)
8
GB
D4007
20126638

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gs20/m2001364220013641

Table of Contents