BEKOMAT
®
12, 12 CO, 12 CO PN63

7.2.3 Connection of external TEST

The BEKOMAT
has an option for the connection of an external TEST button. This enables condensate to be discharged
®
via remote control. If the external contact is closed, the solenoid valve opens like after pressing the TEST button on the
top cover and the BEKOMAT
Illustration
32 | 64
discharges condensate.
®
6 mm (0.23")
60 mm (2.36")
5
6
7
I
4
Normally Open (NO)
Common (CO)
Normally Closed (NC)
±24V
+24 VDC (0 V)
±24V
0 V (+24 VDC)
Original installation and operation manual
Description / explanation
1. Prepare the external TEST button cable.
If the potential free contact is to be connected
in addition to the external TEST button, a 4/5-
wire cable must be used for the connection
(depending on the application).
2. Take the dust protection pane [4] out of the left-hand
cable gland.
3. Slide the components of the cable gland [5, 6, 7] over
the cable [I] and insert the cable into the top cover.
4. Connect the cable of the external TEST button to the
control PCB in accordance with the terminal diagram.