9.1 Operating states

Illustration
n = 20
For further information about fault indications during operation see "15. Troubleshooting / FAQ" on Page 53.
34 | 60
n = 2
n = ∞
Fail-Safe
Original installation and operation manual
Description / explanation
Disconnected
All LEDs are off
Switch on / power-on self-test
All LEDs light up for 1 second
Positive power-on self-test (repeat 2x)
The red Alarm LED is off
The green Valve LED lights up during the solenoid
valve cycles
The green Power LED is on
The solenoid valve cycles
0 goes into normal operation
Negative power-on self-test (repeat 20x)
The red Alarm LED is on
The green Valve LED lights up during the solenoid
valve cycles
The green Power LED is on
The solenoid valve cycles
0 Goes to fail-safe operation (continuous loop)
The solenoid valve cycles once per second
Ready for operation (normal operating mode)
The red Alarm LED is off
The green Valve LED is off
The green Power LED is on
Discharge procedure
The red Alarm LED is off
The green Valve LED lights up during the discharge
procedure
The green Power LED is on
Pre-alarm (permanent loop)
The red Alarm LED flashes
The green Valve LED is on
The green Power LED is on
Alarm
The red Alarm LED is on
The green Valve LED is off
The green Power LED is on