Statistics Menu - BFT U-link LEO B CBB 3 400 W01 Installation Manual

Hide thumbs Also See for U-link LEO B CBB 3 400 W01:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 13
IC logic= 0 - Input configured as Start E. Operation according to STEP-BY-STEP MOV. logic.
IC logic= 1 - Input configured as Start I. Operation according to STEP-BY-STEP MOV. logic.
IC logic= 2 - Input configured as Open.
The command causes the leaves to open. If the input stays closed, the leaves stay open until the contact is opened. When the contact is open, the automated device closes following
the TCA time, where activated.
IC logic= 3 - Input configured as Closed.
The command causes the leaves to close.
IC logic= 4 - Input configured as Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. Operation according to STEP-BY-STEP. logic
IC logic= 5 - Input configured as Timer.
Operation same as open except closing is guaranteed even after a mains power outage.
IC logic= 6 - Input configured as Timer Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. If the input stays closed, the leaf stays open until the contact is opened. If the input stays closed and
a Start E, Start I or Open command is activated, a complete opening-closing cycle is performed before returning to the pedestrian opening position. Closing is guaranteed even after a
mains power outage.
SAFE logic= 0 - Input configured as Phot (photocell). (fig.F, ref.1).
Enables connection of devices not equipped with supplementary test contacts. When beam is broken, photocells are active during both opening and closing. When beam is broken
during closing, movement is reversed only once the photocell is cleared. If not used, leave jumper inserted.
SAFE logic= 1 - Input configured as Phot test (tested photocell). (fig.F, ref.2).
Switches photocell testing on at start of operation. When beam is broken, photocells are active during both opening and closing. When beam is broken during closing, movement is
reversed only once the photocell is cleared.
SAFE logic= 2 - Input configured as Phot op (photocell active during opening only). (fig.F, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during closing. During opening, stops
motion for as long as the photocell beam stays broken. If not used, leave jumper inserted.
SAFE logic= 3 - Input configured as Phot op test (tested photocell active during opening only (fig.F, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during closing. During opening, stops motion for as long as the photo-
cell beam stays broken.
SAFE logic= 4 - Input configured as Phot cl (photocell active during closing only). (fig.F, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during opening. During closing, movement
is reversed immediately. If not used, leave jumper inserted.
SAFE logic= 5 - Input configured as Phot cl test (tested photocell active during closing only (fig.F, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during opening. During closing, movement is reversed immediately.
SAFE logic= 6 - Input configured as Bar (safety edge). (fig.F, ref.3).
Enables connection of devices not equipped with supplementary test contacts. The command reverses movement for 2 sec.. If not used, leave jumper inserted.
SAFE logic= 7 - Input configured as Bar (tested safety edge (fig.F, ref.4).
Switches safety edge testing on at start of operation. The command reverses movement for 2 sec.
SAFE logic= 8 - Input configured as Bar 8k2 (fig.F, ref.5). Input for resistive edge 8K2.
The command reverses movement for 2 sec..
Aux logic= 1 - SCA GATE OPEN LIGHToutput.
Contact stays closed during opening and with leaf open, intermittent during closing, open with leaf closed.
Aux logic= 2 - COURTESY LIGHT command output.
Contact stays on for 90 seconds after the last operation.
Aux logic= 3 - ZONE LIGHT command output.
Contact stays closed for the full duration of operation.
Aux logic= 4 - STAIR LIGHT output.
Contact stays closed for 1 second at start of operation.
Aux logic= 5 - GATE OPEN ALARM output.
Contact stays closed if the leaf stays open for double the set TCA time.
Aux logic= 6 - FLASHING LIGHT output.
Contact stays closed while leaves are operating.
Aux logic= 7 - SOLENOID LATCH output.
Contact stays closed for 2 seconds each time gate is opened.
Aux logic= 8 - MAGNETIC LOCK output.
Contact stays closed while gate is closed.
Aux logic= 9 - MAINTENANCE output.
Contact stays closed once the value set for the Maintenance parameter is reached, to report that maintenance is required.
Aux logic= 10 - FLASHING LIGHT AND MAINTENANCE output.
Contact stays closed while leaves are operating. If the value set for the Maintenance parameter is reached, once the gate has finished moving and the leaf is closed, the contact closes
for 10 sec. and opens for 5 sec. 4 times to report that maintenance is required.
6) SAFETY DEVICES
Note: only use receiving safety devices with free changeover contact.
6.1) TESTED DEVICES Fig. F
6.2) COLLEGAMENTO DI 1 COPPIA DI FOTOCELLULE NON VERIFICATE Fig. C1
6.3) COLLEGAMENTO DI 1 COPPIA DI FOTOCELLULE VERIFICATE Fig. C2
7) CALLING UP MENUS: FIG. 1
7.1) PARAMETERS MENU (PARA ) (PARAMETERS TABLE "A")
7.2) LOGIC MENU (LOGIC) (LOGIC TABLE "B")
7.3) DEFAULT MENU (default)
Restores the controller's DEFAULT factory settings. Following this reset, you will
need to run the AUTOSET function again.
7.4) LANGUAGE MENU (language)
Used to set the programmer's language on the display.
7.5) AUTOSET MENU (AUTOset)
• Launch an autoset operation by going to the relevant menu.
• As soon as you press the OK button, the ".... .... .... " message is displayed and the control
unit commands the device to perform a full cycle (opening followed by closing), dur-
ing which the minimum torque value required to move the leaf is set automatically.
During this stage, it is important to avoid breaking the photocells' beams and not
to use the START and STOP commands or the display.
Once this operation is complete, the control unit will have automatically set the
INSTALLATION MANUAL
Command input configuration
Safety input configuration
AUX output configuration
optimum torque values. Check them and, where necessary, edit them as described
in the programming section.
Warning!! While the autoset function is running, the obstacle detection
function is not active. Consequently, the installer must monitor the
automated system's movements and keep people and property out of
range of the automated system.
7.6) LIMIT SWITCH ADJUSTMENT MENU (L. S W ADJ) (Fig . D)
Limit switch adjustment procedure:
1) Go to L.SW ADJ and confirm with OK.
2) The display reads CLOSE. Use the UP and DOWN keys to move the door to the closing
limit switch position. Confirm with OK. The display reads PRG.
3) If prompted by the display, turn the adjustment ring: anticlockwise if the display
reads UP; clockwise if the display reads DOWN. Once you have reached the correct
position, the display reads OK. Confirm with the OK key. The display reads PRG.
4) The display reads OPEN. Use the UP and DOWN keys to move the door to the opening
limit switch position. Confirm with OK. The display reads PRG.
If the display reads KO, it means adjustment was not successful.
This may be caused by:
- the ESC key being pressed before adjustment was completed
- stored travel being too short

7.7) STATISTICS MENU

Used to view the version of the board, the total number of operations (in
hundreds), the number of transmitters memorized and the last 30 errors (the
first 2 digits indicate the position, the last 2 give the error code). Error 01 is the
most recent.
7.8) PASSWORD MENU
Used to set a password for the board's wireless programming via the U-link network.
15
LEO B CBB 3 400 W 01-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents