Configuration

20.3.2 Available comfort settings

Installer and user reference guide
138
E.g., when your system is operating in cooling, you do not need as much cooling
under low outdoor ambient temperatures (e.g., 25°C) as under high outdoor
ambient temperatures (e.g., 35°C). Using this idea, the system automatically starts
increasing its refrigerant temperature, automatically reducing the delivered
capacity and increasing the system's efficiency.
E.g., when your system is operating in heating, you do not need as much heating
under high outdoor ambient temperatures (e.g., 15°C) as under low outdoor
ambient temperatures (e.g., –5°C). Using this idea, the system automatically starts
decreasing its refrigerant temperature, automatically reducing the delivered
capacity and increasing the system's efficiency.
To activate this in...
Cooling operation
Heating operation
Hi-sensible/economic (cooling/heating)
The refrigerant temperature is set higher/lower (cooling/heating) compared to
basic operation. The focus under high sensible mode is comfort feeling for the
customer.
The selection method of indoor units is important and has to be considered as the
available capacity is not the same as under basic operation.
For details concerning to Hi-sensible applications, please contact your dealer.
To activate this in...
Cooling operation
Heating operation
[2‑8]
3
4
5
6
7
[2‑9]
1
3
For each of above modes a comfort level can be selected. The comfort level is
related to the timing and the effort (energy consumption) which is put in achieving
a certain room temperature by temporarily changing the refrigerant temperature
to different values in order to achieve requested conditions more quickly.
Change...
[2‑8]=0 (default)
[2‑9]=0 (default)
Change...
[2‑8] to the appropriate value, matching
the requirements of the pre-designed
system containing a high sensible
solution.
[2‑9] to the appropriate value, matching
the requirements of the pre-designed
system containing a high sensible
solution.
T
target (°C)
e
7
8
9
10
11
T
target (°C)
c
41
43
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10