5.8

Standard Configurations

5.8.1
Configuration with Single Pipe
5.8.2
Configuration with Tee and Two Pipes
Figure 5-6: Example of IAS-1system with a tee and two pipes.
Distance from unit to Tee must be at most 1 m and pipes should be balanced, be of equal length and have
equal number of holes.
The use of additional bends as described in Section 5.5 will have a minimal effect on performance (response
time) of either configuration.
Note: Please see the table in Section 9 for AS 1603.8 hole and pipe length limits for certified detectors.
These limits describe pre-tested and acceptable system design values for the standard pipe
configurations described in this section, for each type of certified detector.
www.xtralis.com
Figure 5-5: Example of an IAS-1 system with one pipe.
IAS-1 Product Guide
15