Pipe Installation; Pipe Specification; Fixings; Holes - Xtralis ICAM IAS-1 Product Manual

Hide thumbs Also See for ICAM IAS-1:
Table of Contents

Advertisement

ICAM by Xtralis
5

Pipe Installation

This section provides a simple guide to pipe installation and should contain all the information required for
simple installations based on the standard configurations shown in Section 5.8: Standard Configurations.
More information on achieving an ActivFire compliant pipe installation can be found in Section 9: AS 1603.8
Listed Detectors.
Use appropriate CPVC/ABS pipe with sampling point holes drilled along its length. The pipe run is terminated
with an end cap that has a hole drilled in its center.
The position of each individual sampling point should be in accordance with the rules for the positioning of
point detectors. It is important to note that the concentration of smoke on an individual sample point will be
diluted by the clean air from the other sample points and the end cap hole.
5.1

Pipe Specification

For AS 1603.8 compliance, the pipe shall have equal mechanical strength to light duty AS 2053 compliant
PVC conduit. The pipe shall be red, or have a longitudinal red mark at least 2 mm wide along the whole length
of the pipe. The pipe shall be marked with descriptions such as "FIRE DETECTION SYSTEM - DO NOT
PAINT" in letters at least 5 mm high, at intervals of 1 m or less.
Note: The IAS-1 inlet port is tapered to allow a push fit of the sampling pipe. The pipe should be cut squarely
to ensure a good, airtight seal. Solvent adhesive should not be used for this joint.
5.2

Fixings

The normal fixing methods are pipe clips, saddle clamps or even tie wraps. Fixing centers are typically 1.5 m
 (4.9 ft) apart.
5.3

Holes

The sampling pipe is perforated with sampling holes and can either be pre-drilled or drilled in situ. Care should
be taken to avoid swarf entering the pipe. Always blow compressed air through the pipe after drilling to clear
any debris before final connection to the equipment. In standard configuration, with pipe hanging from ceiling,
the holes should be placed underneath, so the smoke can easily rise up into the hole.
5.4

End Cap

The end of the pipe must be capped with an end cap and not be left open. The end cap typically has a
sampling hole drilled in its center to control airflow. For pipes with only a few sampling holes, the end cap hole
usually is the same size as the sampling holes along the pipe. See Section 5.8: Standard Configurations for
approved configurations.
www.xtralis.com
Figure 5-1: End cap with hole drilled in center
IAS-1 Product Guide
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents