DeDietrich ALEZIO S V200 User Manual page 13

Reversible air/water split inverter heat pump
Hide thumbs Also See for ALEZIO S V200:
Table of Contents

Advertisement

Tab.4
Heating mode: outdoor air temperature +7 °C, water temperature at the outlet +35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Heat output
Coefficient of Perform­
ance (COP)
Absorbed electrical pow­
er
Nominal water flow rate
(ΔT = 5K)
Tab.5
Heating mode: outdoor air temperature +2 °C, water temperature at the outlet +35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Heat output
Coefficient of Perform­
ance (COP)
Absorbed electrical pow­
er
Tab.6
Cooling mode: outdoor air temperature +35 °C, water temperature at the outlet +18 °C. Performances in accordance
with EN 14511-2.
Measurement type
Cooling output
Energy efficiency ratio
(EER)
Absorbed electrical pow­
er
Tab.7
Common specifications
Measurement type
Total dynamic head at
nominal flow rate
Nominal air flow rate
Power voltage of the out­
door unit
Start-up amperage
Maximal amperage
Acoustic power - Inner
side
(1)
Acoustic power - Outside dB(A)
Refrigerant fluid R410A
R410A refrigerant
(2)
Refrigerant connection
(Liquid - Gas)
Max. pre-charged length m
(1) Noise radiated by the enclosure - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 55 °C
(except for AWHP 4.5 MR: air 7 °C, water 45 °C inner and outer sides)
(2) The quantity of refrigerant in tonnes of CO
1000. The Global Warming Potential (GWP) of R410A is 2088.
7748661 - v03 - 08062020
Unit
AWHP 4.5
AWHP 6
MR
MR-3
kW
4.60
5.82
5.11
4.22
kWe
0.90
1.38
0.80
1.00
3
m
/h
Unit
AWHP 4.5
AWHP 6
MR
MR-3
kW
3.47
3.74
3.97
3.37
kWe
0.88
1.11
Unit
AWHP 4.5
AWHP 6
MR
MR-3
kW
3.80
4.69
4.28
4.09
kWe
0.89
1.15
Unit
AWHP 4.5
AWHP 6
MR
MR-3
kPa
65
63
2680
2700
3
m
/h
V
230
230
A
5
5
A
12
13
dB(A)
49
49
61
65
kg
1.3
1.4
tCO
e
2.714
2.923
2
inch
1/4 - 1/2
1/4 - 1/2
7
10
equivalent is calculated using the following formula: quantity (in kg) of refrigerant x GWP/
2
AWHP 8
AWHP 11
MR-2
MR-2
7.9
11.39
4.34
4.65
1.82
2.45
1.36
1.96
AWHP 8
AWHP 11
MR-2
MR-2
6.80
10.19
3.30
3.20
2.06
3.19
AWHP 8
AWHP 11
MR-2
MR-2
7.90
11.16
3.99
4.75
2.00
2.35
AWHP 8
AWHP 11
MR-2
MR-2
44
25
3300
6000
230
230
5
5
17
29.5
49
48
67
69
3.2
4.6
6.680
9.603
3/8 - 5/8
3/8 - 5/8
10
10
3 Technical specifications
AWHP 11
AWHP 16
TR-2
MR-2
11.39
14.65
4.65
4.22
2.45
3.47
1.96
2.53
AWHP 11
AWHP 16
TR-2
MR-2
10.19
12.90
3.20
3.27
3.19
3.94
AWHP 11
AWHP 16
TR-2
MR-2
11.16
14.46
4.75
3.96
2.35
3.65
AWHP 11
AWHP 16
TR-2
MR-2
25
6000
6000
400
230
3
6
13
29.5
48
48
69
70
4.6
4.6
9.603
9.603
3/8 - 5/8
3/8 - 5/8
10
10
MIV-S V200
AWHP 16
TR-2
14.65
4.22
3.47
2.53
AWHP 16
TR-2
12.90
3.27
3.94
AWHP 16
TR-2
14.46
3.96
3.65
AWHP 16
TR-2
6000
400
3
13
48
70
4.6
9.603
3/8 - 5/8
10
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents