Safety Instructions; Technical Data - Eaton Crouse-Hinds Series Operating Instructions Manual

Explosion protected led-luminaire
Hide thumbs Also See for Crouse-Hinds Series:
Table of Contents

Advertisement

Available languages

Available languages

1.
Legende
Warning
This symbol warns of a serious hazard.
Failure to observe this warning may result
in death or the destruction of property.
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result
in the total failure of the device or the
system or plant to which it is connected.

1.1 Safety instructions

For skilled electricians and
qualified personnel in accordance
with national legislation, including
the relevant standards and, where
applicable, in acc. with
IEC/EN 60079-14 on electrical apparatus for
explosive atmospheres.
– The light fitting must not be operated in
zone 0, 1 or 20, 21 hazardous areas!
– The technical data indicated on the light
fitting are to be observed!
– The requirements of the
EN/IEC 60079-31 regarding excessive
dust deposits and temperature to be
considered from the user.
– Changes of the design and modifications
to the light fitting are not permitted!
– The light fitting shall be operated as
intended and only in undamaged and
perfect condition!
– Do not keep these operating instructions
inside the light fitting during operation!
The national safety rules and regulations
for pre vention of accidents and the
following safety in structions which are
marked with an (
) in these operating
instruction, will have to be observed!
10
Explosion protected LED­luminaire
Series: EXIT 2 N; zone 2/22
2.

Technical data

Type Examination Certificate:
Marking acc. to 2014/34/EU and standard of series
EN 60079
IECEx Certificate of Conformity:
Category of application standard of series
IEC 60079
Rated voltage:
* the data consider an additional voltage tolerance of ± 10 %
Rated frequency:
Rated current:
Battery:
Charging time:
Duration of emergency lighting:
** Note: New batteries will reach their total useful capacity only after 3 charging/discharging cycles
Insulation class to IEC/EN 60598:
Degree of protection accd. IEC/EN 60529:
Operation temperature:
Storage temperature in original packing:
Weight:
Supply terminal clamping capacity:
Ex­e cable entry
Suitable cables and test torques of the pressure screw Ø cable (mm)
Seal 1+2+3
1 2
3
Seal 1+2
1 2
3
Seal 1
1 2
3
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.
Metal:
Test torque for screw in thread cable entry
Test torque for mounting screws cover:
BVS 15 ATEX E 074
ta max + 40 °C:
II 3 G Ex e ic mc IIC T5 Gc
ta max + 50 °C:
II 3 G Ex e ic mc IIC T4 Gc
II 3 D Ex tc IIIC T80°C Dc
IECEx BVS 15.0065
ta max + 40 °C:
Ex e ic mc IIC T5 Gc
ta max + 50 °C:
Ex e ic mc IIC T4 Gc
Ex tc IIIC T80°C Dc
AC:
110 ­ 277 V *
DC:
110 ­ 250 V *
50 ­ 60 Hz
110 V AC/DC:
approx. 0.06 A
220 V AC/DC:
approx. 0.035 A
Accu 2 x 6 V / 0.8 Ah
28 h
(cap. > 90 %)
3 h **
I
IP 66
­20 °C ... +40 °C / +50 °C
specified data
­5 °C ... +35 °C
­20 °C ... +50 °C
approx. 2.5 kg
2 x per terminal
M20x1.5 (standard version)
min.
5.5
(1)
max.
7 .0
min.
7 .0
(1)
max.
9.0
min.
9.5
(1)
max.
13.0
M20x1.5 thread
2.7 Nm
2.4 Nm
GB
3 x 2.5 mm²
Nm pressure screw
1.5
1.0
1.5
1.4
1.0
1.7