Instruction manual
MTL intrinsic safety solutions
F101, F102, F104
Fieldbus Power Supply
November 2020
INM MTLF10x Rev 1

Advertisement

loading

Summary of Contents for Eaton CROUSE-HINDS Series

  • Page 1 Instruction manual November 2020 MTL intrinsic safety solutions INM MTLF10x Rev 1 F101, F102, F104 Fieldbus Power Supply...
  • Page 2 DECLARATION OF CONFORMITY A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods. However, you can find a copy of the latest version at - http://www.mtl-inst.com/certificates INM F10x Rev 1...
  • Page 3 CONTENTS DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii GENERAL SAFETY INFORMATION .
  • Page 4 No changes to any of the components that might impair their explosion protection are permitted. If any information provided here is not clear: • Contact Eaton’s MTL product line support or one of its representatives. NOTE Improper installation and operation of the enclosure can result in the invalidation of the warranty.
  • Page 5 Figure 1: F101-PS OVERVIEW The F101, F102, and F104 (F10x) Fieldbus Power Supplies are designed to provide power for a single FOUNDATION fieldbus™ H1 or Profibus PA segment. Galvanic isolation, power conditioning and segment termination are incorporated into each F10x module. Termination of the fieldbus segments is normally enabled with a switch on the module, but may be switched off for those few applications that do not require a Terminator at the Fieldbus Power Supply.
  • Page 6 COMPONENTS AND ACCESSORIES Product part numbers and their descriptions are given below. PART No . DESCRIPTION F101-P* Fieldbus Power Supply: 21.5V, 500mA F102-P* Fieldbus Power Supply: 28V, 500mA F104-P* Fieldbus Power Supply: 13V, 250mA PBUS01 Power Bus DIN-rail connectors, pack of 5 PBUS02 Power Bus DIN-rail input plug and socket set PBUS03...
  • Page 7 4 .2 .2 Outdoor Mounting If the F10x is mounted in an outdoor location, use a suitable enclosure with a minimum of IP54 ingress protection. A higher level of ingress protection rating will be necessary if the working atmosphere is or can be corrosive or if the enclosure is subject to wet or dusty environments.
  • Page 8 Figure 4b 4 .4 Removal from DIN-rail To remove the F10x from the DIN-rail, use a screwdriver to release the DIN-rail latching mechanism. Pivot the F10x and remove from the DIN-rail. ELECTRICAL CONNECTIONS The Input power and Fieldbus Segment connectors are pluggable and available in a screw terminal version (-PS) or a spring clamp version (-PC).
  • Page 9 5 .1 DC Power Requirements Power terminals requiring a nominal input voltage of 24VDC are provided allowing the use of bulk power supplies with a supply range of 19.2–30VDC (10–30VDC for the F104). Input power cabling and over-current protection devices must be chosen to match the current consumption.
  • Page 10 5 .3 DIN-rail bussing Rather than using the top 4 way connectors to provide power to the F10x, an optional DIN-rail bussing system is available. This is very convenient when multiple F10x units are in the same cabinet. One DIN-rail bussing connector is needed for each F10x module.
  • Page 11 5 .5 Fieldbus Connections There are two 3 way connectors (internally wired together) for connection to a Host and Field cable. Each connector provides (+), (–) and cable screen (S) connections. See section 5.6 for information on cable screen grounding. Pin No .
  • Page 12 ROUTINE MAINTENANCE Check the general condition of the installation occasionally to make sure that no deterioration has occurred. At least every two years (and more frequently for particularly harsh environments) check: • the condition of wire connections, terminations, and screens. •...
  • Page 13 FM CONTROL DRAWINGS HAZARDOUS (CLASSIFIED) LOCATION WARNING - EXPLOSION HAZARD. DO NOT DISCONNECT Class I, Division 2, Groups ABCD T4 EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE Class I, Zone 2, IIC T4 (US only) ATMOSPHERE IS PRESENT. Ex nA nL IIC T4 (Canada only) -40°C Tamb 65°C...
  • Page 14 FM Special Conditions of Use 1. In Class I, Division 2 installations, the subject equipment shall be mounted within a tool secured enclosure which is capable of accepting one or more of the Class I, Division 2 wiring methods specified in the National Electrical Code (ANSI/NFPA 70) for US installations –...
  • Page 15 This page left intentionally blank INM F10x Rev 1...
  • Page 16 AUSTRALIA NORWAY Eaton Electrical (Australia) Pty Ltd, Norex AS 10 Kent Road, Mascot, New South Wales, 2020, Australia Fekjan 7c, Postboks 147 , N-1378 Nesbru, Norway Tel: +61 1300 308 374 Fax: +61 1300 308 463 E-mail: mtlsalesanz@eaton.com Tel: +47 66 77 43 80 Fax: +47 66 84 55 33 E-mail: info@norex.no...