CD Automation REVEX 2PH 280A User Manual page 31

Table of Contents

Advertisement

REVEX
2PH 280A
Parameter Name
Pb Power
Set the gain for the main loop. A larger
value yields a larger adjustment for a
given deviation
Ti Power
Set how aggressively the integral part
of the control algorithm acts. A larger
settings yields a larger adjustment for
a given deviation over a given time
HB Sense
Set the threshold of resistance that
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
HB Delay
Set a delay between when the
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
Description
31
Default
Range
10%
0 to 255
50
0 to 255
100%
0 to 100.0
0 to 255
50 (2,5
(0 to 12,75
sec)
sec)
User's manual
Modbus
Par.
Unit
Address
Type
Read
%
26
Write
Read
27
Write
Read
%
29
Write
Read
28
Write

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the REVEX 2PH 280A and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

M-rx2-280Revex m-rx2-280

Table of Contents