Preparations for use
4.15 Converter operation
①
②
③
Figure 4-2
NOTICE
Bearing damage
The bearing insulation must not be bridged. Bearing currents can damage bearings.
● Also for subsequent installation work, such as the installation of an automatic lubrication
● Contact the Service Center, if necessary.
Tandem operation
If you connect two motors in series in "tandem operation", install an insulated coupling between
the motors.
①
②
③
Figure 4-3
NOTICE
Bearing damage
Bearing currents can flow if the coupling between the motors of the tandem drive is not
insulated. This can damage the DE bearings of both motors.
● Use an insulated coupling to link the motors.
42
Driving machine
Motor
Coupling
Schematic representation of a single drive
system or a non-insulated vibration sensor, make sure that the bearing insulation cannot
be bridged.
Driving machine
Motor
Coupling
Schematic representation of a tandem drive
④
Insulated bearings
⑤
Insulated tachometer fitting
④
Insulated bearings
⑤
Insulated tachometer fitting
⑥
Insulated coupling
SIMOTICS TN Series N-compact 1LL8
Operating Instructions 11/2018