Capacity Compensation Rate For Pipe Length And Height Difference; Model: Aou24Rlxfz - Fujitsu AUU7RLF Design & Technical Manual

Refrigerant r410a inverter, multi: 2, 3, 4 rooms type, indoor/outdoor
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

7. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

7-1. Model: AOU24RLXFZ

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢ Indoor unit: 7,000 Btu
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
7-1. Model: AOU24RLXFZ
Height difference H
1
*
H
Outdoor unit
m
m
ft
15
49
10
33
7.5
25
5
16
0.995
0
0
1.003
-5
-16
1.003
-7.5
-25
-10
-33
-15
-49
m
m
ft
15
49
10
33
7.5
25
5
16
0.990
0
0
0.990
-5
-16
0.985
-7.5
-25
-10
-33
-15
-49
- 237 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length
5
7.5
10
16
25
33
-
-
-
-
-
0.977
-
0.988
0.981
0.992
0.985
1.000
0.993
1.000
0.993
-
1.000
0.993
-
-
0.993
-
-
-
Pipe length
5
7.5
10
16
25
33
-
-
-
-
-
0.993
-
1.000
0.993
1.000
0.993
1.000
0.993
0.995
0.988
-
0.993
0.986
-
-
0.983
-
-
-

7. Capacity compensation rate for pipe length and height difference

2
*
15
20
25
49
66
82
0.956
0.942
0.928
0.963
0.950
0.936
0.967
0.953
0.940
0.971
0.957
0.943
0.979
0.965
0.951
0.979
0.965
0.951
0.979
0.965
0.951
0.979
0.965
0.951
0.979
0.965
0.951
15
20
25
49
66
82
0.977
0.958
0.939
0.977
0.958
0.939
0.977
0.958
0.939
0.977
0.958
0.939
0.977
0.958
0.939
0.972
0.953
0.934
0.970
0.951
0.932
0.967
0.948
0.930
0.962
0.944
0.925