1. Specifications

1-1. Model: AOU36RLXFZ1

Type
Model name
Power source
Available voltage range
Connectable indoor unit
Combination of indoor unit
Cooling
Capacity
Heating
Cooling
Input power
Heating
Cooling
Current
Heating
EER
Cooling
1
Cooling
SEER *
COP
Heating
1
Heating
HSPF *
Starting current
2
Maximum operating current *
Type × Q'ty
Cooling
Airflow rate
Fan
Heating
Type × Quantity
Motor
Output
Cooling
Sound pressure level
Heating
Dimension (H × W × D)
Fin pitch
Rows × Stages
Heat exchanger
Pipe type (Material)
Fin
Type × Quantity
Compressor
Motor output
Type
Refrigerant
Charge
Type
Refrigerant oil
Amount
Material
Enclosure
Color
Net
Dimensions
(H × W × D)
Gross
Net
Weight
Gross
Liquid
Size
Gas
Method
Pre-charge length (Total)
Max. length (Total)
Connection pipe
Max. length (Each)
Min. length (Total)
Min. length (Each)
Max. height difference between outdoor unit and each
indoor units
Max. height difference between indoor units
Cooling
Operation range
Heating
NOTES:
• Specifications are based on the following conditions:
– Power source of specifications : 230 V
– Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit—Indoor unit]
– Cooling: Indoor temperature of 80 °FDB (26.7 °CDB)/67 °FWB (19.4 °CWB), and outdoor temperature of 95 °FDB (35°CDB)/75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.1 °CDB)/60 °FWB (15.6 °CWB), and outdoor temperature of 47 °FDB (8.3 °CDB)/43 °FWB (6.1 °CWB).
– *1: Test conditions are based on AHRI 210/240.
– *2: The maximum current is the maximum value when the operated within the operation range.
• *, **: When AOU36RLXFZ1 is paired with two 18,000-Btu indoor units, you have to purchase optional part K9FZ1818 (UTP-MU36A2) kit. [Its pre-charge length is 66 ft (20 m)].
• For other combination, refer to the combination table.
• The protective function might work when using it outside the operation range.
1-1. Model: AOU36RLXFZ1
Number
Total capacity range
Btu/h
Rated
kW
Btu/h
Min.—Max.
kW
Btu/h
Rated
kW
Btu/h
Min.—Max.
kW
Rated
Max.
kW
Rated
Max.
Rated
A
Rated
Btu/W
-
Rated
W/W
-
A
A
3
CFM (m
/h)
W
Rated
dB (A)
in (mm)
FPI
Type (Material)
Surface treatment
W
lb (g)
3
3
in
(cm
)
in (mm)
lb (kg)
in (mm)
ft (m)
°F (°C)
- 248 -
Inverter heat pump
AOU36RLXFZ1
1Ø 208/230 V 60 Hz
187—264V
2* to 4
27,000 to 39,000 Btu/h
Non-duct
Duct
ASU9RLF1 × 4
ARU9RLF × 4
35,200
10.3
11,000—38,000
3.2—11.1
36,400
10.68
11,000—42,000
3.2—12.3
3.52
3.92
4.10
4.38
3.00
3.22
3.70
3.85
15.4
17.1
13.1
15.1
10.0
9.0
18.0
16.0
3.56
3.32
9.4
8.7
17.1
20.3
Propeller × 1
2,119 (3,600)
2,237 (3,800)
DC motor × 1
100
53
55
31-13/32 × 35-7/16 × 1-7/16 (798 × 900 × 36.38)
20
2 × 38
Grooved H-pin (Copper)
Corrugate (Aluminum)
Corrosion resistance (Blue Fin)
DC twin rotary × 1
2,100
R410A
7 lb 1 oz (3,200)
RB68
48.8 (800)
Painted galvanized steel
Beige
(Approximate color of Munsell 10YR 7.5/1.0 NN)
32-11/16 × 35-7/16 × 13 (830 × 900 × 330)
39-3/8 × 41-5/16 × 17-1/2 (1,000 × 1,050 × 445)
149 (68)
168 (76)
Ø1/4 (Ø6.35) × 4
Ø3/8 (Ø9.52) × 3 + Ø1/2 (Ø12.7) × 1
Flare
164 (50)**
230 (70)
82 (25)
66 (20)
16 (5)
49 (15)
33 (10)
14 to 115 (-10 to 46)
5 to 75 (-15 to 24)
Mix
3.71
4.24
3.11
3.78
15.9
14.1
9.5
17.0
3.44
9.1