Safety Devices - Fujitsu AUU7RLF Design & Technical Manual

Refrigerant r410a inverter, multi: 2, 3, 4 rooms type, indoor/outdoor
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

12. Safety devices

Type of protection
Circuit protection
Fan motor protection
Compressor protection
Refrigerant circuit
protection
Pressure switch 2: For control device. (Refer to the wiring diagram.)
*: Only for cooling or dry operation.
Protection form
Current fuse
(Main PCB)
Current fuse
(Near the terminal)
Temperature thermistor
Temperature thermistor
Thermal protection program
(Outdoor temp.)*
Pressure switch 1
- 244 -
AOU24RLXFZ
250 V, 3.15 A
250 V, 10 A
Activate
(150 ±15 °C)
Fan motor stop
Reset
(120 ±15 °C)
Fan motor restart
Activate
(110 ±2 °C)
Compressor stop
Reset
Compressor restart
Activate
Compressor stop
Reset
609 ±15 PSI
Activate
(4.2 ±0.1 MPa)
464 ±22 PSI
Reset
(3.2 ±0.15 MPa)
Model
250 V, 5 A
302 ±27 °F
248 ±27 °F
230 ±4 °F
176 ±4 °F
(80 ±2 °C)
-15 °C
12. Safety devices