Exchange Of Piping Direction (Drain Hose) - Daikin FTK15JEVM Service Manual

Removal procedure 1.5/2.0/2.5/3.2/3.5/4.6 kw class 9000/12000 btu/h class
Table of Contents

Advertisement

Exchange of Piping Direction (Drain Hose)

11.Exchange of Piping Direction (Drain Hose)
Procedure
Step
1
Remove the heat
insulation fixing screw
on the right side and
remove the drain hose.
Remove the drain plug
2
located at the left side
with pliers and insert
the removed drain plug
into the right side with a
hexagonal wrench (4
mm).
Insert the drain hose to
3
the left side, and tighten
it with the heat
insulation fixing screw.
30
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Drain plug
Drain piping (left)
Drain hose
Heat insulation fixing screw
(R8054)
(R8055)
(R8056)
(R8057)
Si041051
Points
Caution
Do not thrust in the drain
plug with a sharp-pointed
tool like a screwdriver. (The
drain plug may be broken,
resulting in water leakage.)
After removing the drain
hose, to prevent water
leakage, make sure to
mount the heat insulation
fixing screw as it was.
Removal Procedure