Drain Piping; Refrigerant Piping Work; Flaring The Pipe End - Daikin ATX35J2V1B Installation Manual

Hide thumbs Also See for ATX35J2V1B:
Table of Contents

Advertisement

Indoor Unit Installation
6.

Drain piping.

1) Connect the drain hose, as described right.
2) Remove the air filters and pour some water into the drain pan to check the water flows
smoothly.
3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.
[Figure of Hose Front End]
4) When extending the drain hose, use a commercially available
extension hose with an inner diameter of 16 mm. Be sure to
thermally insulate the indoor section of the extension hose.
5) When connecting a rigid polyvinyl chloride pipe
(nominal diameter 13mm) directly to the drain
hose attached to the indoor unit as with
embedded piping work, use any commercially
available drain socket (nominal diameter 13mm)
as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
10
ø16
ø18
The drain hose provided
to indoor unit.
ø18
The drain hose provided
Commercially available drain
to indoor unit.
socket
(nominal diameter 13mm)
(Cut exactly at
right angles.)
Set exactly at the position shown below.
A
Flare tool for R410A
Clutch-type
A
0-0.5mm
Die
Indoor unit
drain hose
ø16
Heat insulation tube
(Field supply)
Commercially available rigid
polyvinyl chloride pipe
(nominal diameter 13mm)
Remove burrs
Flaring
Conventional flare tool
Clutch-type (Rigid-type)
Wing-nut type (Imperial-type)
1.0-1.5mm
Check
Flare's inner surface
must be flaw-free.
The drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
Extension drain hose
1.5-2.0mm
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
English

Advertisement

Table of Contents
loading

Table of Contents