Example Of Heating And Cooling Demand Zone - Siemens DF301 Basic Documentation

Semi-flush mount communicating room thermostats
Table of Contents

Advertisement

RMH760
Controller 1
T
T
T
Heat source
DHW heating
Heat requistion
Heat demand
Heat distr zone 1
Setting values
Controller 1
Explanation relating to
the illustration
Note:
Siemens.........................RDF301, RDF301.50..., RDF600KN, RDF600KN/VB, RDF600KN/S
Smart Infrastructure

3.11.4 Example of heating and cooling demand zone

The building is equipped with Synco controls on the generation side and RDF /
RDG thermostats on the room side.
RMH760
Controller 3
Controller 2
2
T
1
Heating circuit
fan coil
Heat demand
Heat requistion
Heat distr zone
source side: 1
Heat distr zone 2
Controller 2
Controller 3
In the case of a typical application, the individual RDF / RDG room thermostats
send their heat demand directly to the primary controller (in the above example to
the RMH760).
(1) and (2) designate the numbers of the distribution zone.
· This type of application can analogously be applied to refrigeration distribution
zones.
· If no 2-pipe fan coil is used, heat and refrigeration demand signals are sent
simultaneously to the primary plant.
RMB795
RDF...
Controller 4
T
Fan coil
room A
Heat demand
Heat distr zone 2
Controller 4
Basic Documentation
Konnex TP1
RDU...
RDG...
Controller 5
Controller 6
T
V
V M
M
T
VAV box
Fan coil
room B
room C
Heat demand
Heat demand
Heat distr zone 2
Heat distr zone 2
Controller 5
Controller 6
CE1P3171en
2020-02-21
57 / 92