Siemens DF301 Basic Documentation page 22

Semi-flush mount communicating room thermostats
Table of Contents

Advertisement

Example 2 (RDF301...)
Time schedule
Room operating
mode
Operating mode
button on the
thermostat
Window contact
Room 2
Effective room
operating mode
Room 2
22 / 92
Siemens...........................RDF301, RDF301.50..., RDF600KN, RDF600KN/VB, RDF600KN/S
Smart Infrastructure
Interaction of user operation (operating mode button) and central time
schedule
In room 2, the window is opened briefly, once in the morning and once at night (1).
Only the opening in the morning has a direct impact on the effective room opera-
ting mode.
With the operating mode button, the operating mode can be changed between
OFF and Auto or temporary Comfort extension respectively.
·
During lunch break, the time schedule changes to Pre-Comfort. The mode of
the thermostat changes to Economy as set by parameter "Transformation Pre-
Comfort". (P88 = 0) (6)
·
During lunch break, the user changes the operating mode to Comfort
(temporary Comfort extension) by pressing the operating mode button. (2)
At 13:00, the timer is reset due to mode change of the central time schedule
·
In the afternoon, the user switches the thermostat off by pressing the operating
mode button. (3) At 17:00 the user setting is reset to Economy by the time
schedule.
·
At 19:30, the user again extends the Comfort mode (4). At 20:00, the timer is
reset by the time schedule.
·
After 20:00, pressing the operating mode button has no effect, as the central
time switch sets the thermostat to Protection. (5)
Comfort
Pre-Comfort
Economy
Protection
Pressed
Window open
Window closed
Comfort
Economy
Protection
12:00
13:00
06:00
08:00
2)
1)
6)
Basic Documentation
17:00
20:00
3)
4)
5)
1)
CE1P3171en
2020-02-21