Siemens DF301 Basic Documentation page 26

Semi-flush mount communicating room thermostats
Table of Contents

Advertisement

Protection mode
Caution
26 / 92
Siemens...........................RDF301, RDF301.50..., RDF600KN, RDF600KN/VB, RDF600KN/S
Smart Infrastructure
Use control parameters P65 and P66 to adjust the Protection mode setpoints.
The heating setpoint is factory-set to 8 °C (frost protection) and to OFF for cooling.
If a setpoint (Economy or Protection) is set to OFF, the thermostat does not control
the room temperature in the corresponding mode (heating or cooling).
This means no protective heating or cooling function and thus risk of frost in
heating mode or risk of overtemperature in cooling mode!
The Economy setpoints are accessible at the service level (P11, P12); the
Protection setpoints at the expert level (P65, P66).
Basic Documentation
CE1P3171en
2020-02-21