The BSI series boilers are low pressure cast iron gas fired steam boilers designed for use in closed steam heating systems
at steam pressures below 15psi. These boilers are Category I draft diverter equipped appliances, which must be vented by
natural draft using a lined masonry or listed metal chimney system. An adequate supply of air for combustion, ventilation and
dilution of flue gases must be available in the boiler room. These boilers are not designed for use in process or other "open"
steam systems.
FIGURE 2.1: BSI BOILERS - GENERAL CONFIGURATION
TABLE 2.2: BSI SPECIFICATIONS
BSI SPACE HEATING RATINGS
NATURAL AND LP GAS
CROWN
HEATING
INPUT
MODEL
CAPACITY
(MBH)
NUMBER
(MBH)
BSI069
69
BSI103
103
BSI138
138
113
BSI172
172
142
BSI207
207
171
BSI241
241
199
BSI276
276
229
1. Not for use at altitudes above 2,000 ft. in natural or LP gas.
Available as semi-packaged boiler.
I Product Description
II Specifications
AHRI NET RATING STEAM
(MBH)
SQ. FT.
57
179
85
267
354
446
533
621
717
NO. OF
SEC.
AFUE
(%)
MBH
43
82.0
3
64
82.0
4
85
82.0
5
107
82.1
6
128
82.1
7
149
82.2
8
172
82.2
9
1 1
DIMENSIONS
"A"
"B"
"C"
(in)
(in)
(in)
12-3/4
28
40-7/16
16
28
40-7/16
19-1/4
28
40-7/16
22-1/2
28
40-7/16
25-3/4
30
40-7/16
29
30
40-7/16
32-1/4
30
40-7/16
WATER
VOLUME
"D"
(Gal.)
(in)
4
5.1
5
6.5
6
7.9
6
9.3
7
10.7
7
12.1
8
13.5

Hide quick links: