Start-up
Measure Static Pressure and Running Pressure
IMPORTANT
A CO
measurement (see page 28) must be taken before
2
and after working on gas appliances to eliminate risks to
health and to guarantee the satisfactory condition of the
system.
IMPORTANT
The burner is automatically ignited and starts operation
after a safety time has elapsed. During initial start-up,
the unit may indicate a fault because of air in the gas
supply pipe (especially for liquid propane gas). After
approx. 5 seconds, press the "R" button to reset the
burner. The ignition procedure is repeated. This boiler
employs a direct spark ignition system.
WARNING
Ensure that there is no open flame in the room.
18
Vitocrossal 300 CU3A 26 to 199 Service
1. To measure static and/or running pressure remove
boiler enclosure panel as indicated page 11 in these
instructions.
2. Close gas shutoff valve (field supplied).
3. Loosen screw at inlet gas pressure port A on the
gas combination valve, do not remove completely.
Connect manometer.
4. Open the gas shutoff valve.
5. Measure static pressure. Values must be:
14 "w.c. maximum for NG
14 "w.c. maximum for LPG
6. Enter measured value into Maintenance Record on
page 113 in this manual.
7. Start up boiler, using the ON/OFF switch "8" on the
boiler control.
Note: Flip up lower orange cover to access the ON/
OFF switch.
8. Measure the running pressure; value must be:
Note: Use suitable measuring instruments calibrated
with a minimum resolution of 0.04 "w.c. for
measuring the running pressure.
Running supply pressure with
NG
LPG
under 4 "w.c. under 4 "w.c.
4 to 14 "w.c. 10 to 14 "w.c.
over 14 "w.c. over 14 "w.c.
9. Enter gas type into Maintenance Record on page 113
in this manual.
10. Switch off the ON/OFF switch "8" on the boiler
control, close the gas shut-off valve, remove the
manometer and re-tighten the screw at inlet gas
pressure port A.
WARNING
Never purge a gas line into a combustion chamber.
Never use matches, candles, flame, or other sources of
ignition for purpose of checking leakage. Use a soap and
water solution to check for leakage. A failure to follow
this warning could result in fire, explosion, personal
injury or death.
Corrective action
Do not start the boiler.
Notify your gas supply
utility or LPG supplier.
Start up boiler.
Do not attempt
adjustment. Call local
gas utility to decrease
pressure or install up
stream gas pressure
regulator. Boiler valve
must not be exposed to
pressure over 14 "w.c.