Zone Heating Circuit 1, 2 And 3 - Viessmann Vitocrossal 300 Series Service Instructions Manual

Floor mounted, gas-fired condensing boiler with matrix gas burner and lambda pro control
Hide thumbs Also See for Vitocrossal 300 Series:
Table of Contents

Advertisement

Vitocrossal 300 CU3A 26 to 199 Service
Zone Circuit 1, 2 and 3
Coding in the factory setting
1B:14
1C:0
68:14
69:0
6A:14
6B:0
Heating curve slope = 1.4
Heating curve level = 0
Heating curve slope = 1.4
Heating curve level = 0
Heating curve slope = 1.4
Heating curve level = 0
Possible change
1B:2
Heating curve slope adjustable
to
from 0.2 to 3.5.
1B:35
Zone circuit 1
1C:–13
Heating curve level adjustable from
to
-13 to 40.
1C:40
Zone circuit 1
68:2
Heating curve slope adjustable
to
from 0.2 to 3.5.
68:35
Zone circuit 2
69:–13
Heating curve level adjustable from
to
-13 to 40.
69:40
Zone circuit 2
6A:2
Heating curve slope adjustable
to
from 0.2 to 3.5.
6A:35
Zone circuit 3
6B:–13
Heating curve level adjustable from
to
-13 to 40.
6B:40
Zone circuit 3
Coding 2
81