Advertisement

Vitocrossal 300 CU3A 26 to 199 Service

Boiler

Coding in the factory setting
06:95
0D:0
0E:0
13:1
14:1
15:1
21:0
23:0
24:0
2E:0
38:0
Maximum limit of the boiler
water temperature, specified
in °C by the boiler coding card
DO NOT ADJUST
DO NOT ADJUST
DO NOT ADJUST
DO NOT ADJUST
DO NOT ADJUST
No service interval (hours run)
selected
No time interval for burner
service
No "Service" display
DO NOT ADJUST
Status burner control unit:
Operational (no fault)
Possible change
06:20
Maximum limit of the boiler water
to
temperature within the ranges
06:127
specified by the boiler.
--
--
--
--
--
21:1
Number of hours run before the
to
burner should be serviced is
21:100
adjustable from 100 to 10,000 h
One adjusting step K 100 h.
23:1
Interval adjustable from 1 to 24
to
months.
23:24
24:1
"Service" display (the address is
automatically set and must be
manually reset after a service has
been carried out).
--
38:≠0
Status burner control unit: Fault.
Coding 2
--
--
--
--
--
--
69