Viessmann Vitocrossal 300 Series Service Instructions Manual page 95

Floor mounted, gas-fired condensing boiler with matrix gas burner and lambda pro control
Hide thumbs Also See for Vitocrossal 300 Series:
Table of Contents

Advertisement

Vitocrossal 300 CU3A 26 to 199 Service
Corrective Action
Temperature sensors
(continued)
Checking the flue gas temperature sensor
The flue gas temperature sensor locks out the boiler
when the permissible flue gas temperature is exceeded.
Reset the interlock after the flue system has cooled
down by pressing reset button R.
1.
Pull the leads from flue gas temperature sensor A.
2.
Check the sensor resistance and compare it with
the curve.
3.
Replace the sensor in the case of severe deviation.
Checking the boiler fuse
1. Switch off the power.
2. Remove top panel and cover (see page 93).
3. Check fuse F1 (see connection and wiring diagram).