Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following
prompts are displayed:
∗ ∗ ∗ ∗ 79 Menu Mode
PROMPT
ENTER OUTPUT NO.
00 = QUIT
xx
17 OUT NORM LOW
0 = NO 1 = YES
0
XX OUTPUT TYPE
DELETE
0
"A"
XX UNIT No.
yy
"B"
XX MODULE ADDR
07-15
yy
XX REL POSITION
1-4
zz
6-2
VALID ENTRIES
Device Output Number
01-18 = FA168CPS relays/X-10
01-08, 17, 18 = FA148CP
relays/X-10
[∗] to continue
Output Normally Low
0 = no (standard default)
1 = yes
[∗] to continue
Output Type
0 = delete
1 = relay on 4204/4229 module
2 = Powerline Carrier device
[∗] to continue
Unit Number
01-16 = predefined address
[∗] to continue
Module Address
07-15 = predefined address
[∗] to continue
Relay Position
1-4 = relay position
[∗] to continue
EXPLANATION
This is the logical (or reference) relay number as used in the system.
Relays and X-10 devices are numbered 01-16; the on-board triggers
are numbered 17 and 18 and can be programmed for inverted output.
Use the worksheet on the Programming Form (printed separately) to
organize device numbers.
This prompt appears only for Triggers 17 and 18.
Selecting 0 (no) sets the output level normally high.
Selecting 1 (yes) sets the output normally low.
Output Trigger 17 can be used for resetting 4-wire smoke detectors
by connecting it to the negative power terminal of the smoke
detector, selecting 1 at this prompt, and setting as zone type 54, fire
zone reset, in *80 Menu mode.
After entry, display returns to Output Number prompt. Use *80
Menu mode to program the function of the trigger.
Select whether this is a relay or a Powerline Carrier (X-10) device.
If Powerline Carrier is selected, go to "A" prompt.
If relay is selected, skip to "B" prompt.
If X-10 is selected, a prompt for the unit number appears.
Enter the unit code (set at the device) and press [∗].
The system returns to the Output Number prompt.
If relay is selected, this prompt appears.
Enter the predefined address for this module as listed below. Make
sure the module's DIP switches are set to the selected address.
Module Addresses
Address Module
07
1st 4229 (with zones 09-16)
08
2nd 4229 (with zones 17-24)
09
3rd 4229 (with zones 25-32)
10
4th 4229 (with zones 33-40)
11
5th 4229 (with zones 41-48)
12
1st 4204
13
2nd 4204
14
3rd 4204
15
4th 4204
This is the actual (or physical) relay number with respect to the
Relay Module upon which it is located. For 4204 modules, relay
numbers are 1-4. For 4229 modules, relay numbers are 1-2.
The system returns to the Output Number prompt for programming
the next device.
† These addresses
apply to the FA168CPS
only.