System Power Specifications; Environmental Requirements - Brocade Communications Systems 6505 Hardware Reference Manual

Table of Contents

Advertisement

DRAFT: BROCADE CONFIDENTIAL
A

System power specifications

TABLE 6
.
Type
Electrical
Thermal
Cabinet (when
rack-mounted)

System power specifications

The power supplies are universal and capable of functioning worldwide without voltage jumpers or
switches. They meet IEC 61000-4-5 surge voltage requirements and are autoranging in terms of
accommodating input voltages and line frequencies. Each power supply has built-in fans for
cooling.
Table 7
TABLE 7
Specification
Maximum output (per power supply)
AC input power draw
AC input voltage
AC input line frequency
AC inrush current
Input line protection

Environmental requirements

Table 8
during transportation or storage) conditions.
TABLE 8
Condition
Ambient
Temperature
Humidity
32
Facility Requirements
Requirements
Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating
on the switch nameplate.
Circuit protected by a circuit breaker and grounded in accordance with local electrical
codes.
Refer to
Table 7 on page 32
A minimum air flow of 79.8 cubic meters/hour (47 cubic ft/min.) available in the
immediate vicinity of the switch.???
Ambient air temperature not exceeding 40
One rack unit (1U) in a 48.3 cm (19-inch) cabinet.
All equipment in cabinet grounded through a reliable branch circuit connection.
Additional weight of switch not to exceed the cabinet's weight limits.
Cabinet secured to ensure stability in case of unexpected movement.
lists the system power specifications for the Brocade 6505.
System power specifications
lists the acceptable environmental ranges for both operating and nonoperating (such as

Environmental requirements

Acceptable during operation
0º to 40ºC (32º to 104ºF)
10% to 85% RH non-condensing, at
40ºC (104ºF)
for complete power supply specifications.
°
C (104
Value
150 watts, 12 VDC
Idle, no optics: 60 W
Maximum, fully populated with 16 Gbps SWL optics: 80 W
85-264 VAC, nominal 100-240 VAC
47-63 Hz, nominal 50-60 Hz
Maximum of 35A @ 240 VAC for 10ms or less
AC lines are fused
Acceptable During Non-Operation
-25º to 70ºC (-13º to 158ºF)
10% to 90% RH non-condensing, at 70ºC
(158ºF)
Brocade 6505 Hardware Reference Manual
°
F) while the switch is operating.
53-1002449-01