2
Installation and safety considerations
3. In an two-post Telco rack using the mid-mount rack kit for switches. The mid-mount rack
4. In an EIA rack using a four-post sliding rail rack kit. The sliding rail rack mount kit can be

Electrical considerations

To install and operate the switch successfully, ensure the following:

Power supply specifications

The power supplies are universal and capable of functioning worldwide without voltage jumpers or
switches. They meet IEC 61000-4-5 surge voltage requirements and are autoranging in terms of
accommodating input voltages and line frequencies. Each power supply has built-in fans for
cooling.
Table 1
TABLE 1
Specification
Input voltage
Input frequency
Inrush current
Input line protection
Maximum power supply output (each)
Maximum current
System power consumption (240VAC input)

Environmental considerations

For successful installation and operation of the switch, ensure that the following environmental
requirements are met:
6
DRAFT: BROCADE CONFIDENTIAL
kit for switches can be ordered from your switch retailer.
ordered from your switch retailer.
The primary outlets are correctly wired, protected by a circuit breaker, and grounded in
accordance with local electrical codes.
The supply circuit, line fusing, and wire size are adequate, as specified by the electrical
rating on the switch nameplate.
The power supply standards provided in
lists the power supply specifications for the Brocade 6520.
Power Supply Specifications
At a minimum, adequate cooling requires that you install the switch with the intake side,
as indicated by the airflow direction of the fan assemblies, facing the cool-air aisle.
All equipment in the rack should force air in the same direction to avoid intake of exhaust
air.
A maximum of 102 cubic meters/hour (60 cubic feet/minute) and a minimum of 74.8
cubic meters/hour (44 cubic feet/minute) of air flow is available for air intake.
Table
1,
"Power Supply Specifications"
Value
Range: 85-264 VAC Auto-volt, Nominal: 100-240 VAC, ~5.0A - 2.5A;
switch autosenses input voltage.
Range: 47-63 Hz; Nominal: 50-60 Hz.
Limited to 40A peak @ 240Vac for any initial current surge or spike
of 10ms or less at cold start-up at 25º C ambient.
Both AC lines are fused.
1100 watts @ 12V DC
41.4A @ 12V DC.
456 W with all 96 ports populated with 16 Gbps SWL optics
247 W with empty chassis and no optics.