Power Specifications - Brocade Communications Systems DCX 8510-8 Hardware Reference Manual

Backbone
Hide thumbs Also See for DCX 8510-8:
Table of Contents

Advertisement

A

Power specifications

The ports are universal and self-configuring, capable of becoming F_Ports (fabric ports), FL_Ports
(fabric loop-enabled ports), or E_Ports (expansion ports).
The ports meet all required safety standards. For a listing of these standards, see
compliance".

Power specifications

The power subsystem is a redundant +48V DC power distribution system with a provision for up to
four 2000-watt, 48V DC bulk power supplies. Four bulk power supplies produce the intermediate
distribution voltage in the distributed power system.
If circuits are available, 200-240 VAC (220 VAC nominal) is always recommended as a greener and
more efficient alternative.
NOTE
If any of the following intelligent blades are used, 200-240 VAC is required:
FS8-18, FX8-24.
TABLE 22
.
Specification
Input voltage
Input frequency
Inrush current
Power supply output (each)
The power requirements for a given configuration depend on which blades have been installed in
the chassis. The following table shows the power draw for the blades that can be used in the
Brocade DCX 8510-8 chassis along with the power draw for the cooling fans.
All numbers for the blades assume that the blade is fully populated with optical transceivers,
including QSFPs for the core blades. All ports are Fibre Channel except where noted.
You can calculate your power requirements by combining the power draws for the various blades
and fan units in your configuration. While you may use fewer ports in a given blade, it is always
safer to use the power requirement of a fully populated blade.
TABLE 23
Blade or fan
units
CP8
CR16-8
FC16-32
(16Gb)
120
Power specifications
Value
Range: 85-264 VAC Auto-volt, Nominal: 100-240 VAC.
Range: 47-63 Hz; Nominal: 50-60 Hz.
Limited to 60A peak for any initial current surge or spike of 10ms or less at
either cold or warm start. Any additional inrush current surges or spikes in
the form of AC cycles or multiple AC cycles greater than 10ms, and less than
150ms, must not exceed 15A peak.
Low line (85-132 VAC), 1000W; High line (180-264 VAC), 2000W.
Power demands per component
Maximum
Type of Blade Ports per blade
Power Draw
(Watts)
40
Control
blade
240
Core blade
140
Port blade
Number of blades
permitted in chassis
NA
2
16 64 Gbps QSFP
2
ports
32 16 Gbps SFP+
up to 8
-can use 8 Gbps
SFP+
Brocade DCX 8510-8 Backbone Hardware Reference Manual
"Regulatory
Total ports per chassis
NA
32 quad ports (128
ports)
256
53-1002180-03