Synchronisation Gate Time (06. Menu Item) - Datcon DT9102 I4 Operating Instructions Manual

Intrinsically safe digital clock
Table of Contents

Advertisement

DT9102 I4
Function
Sequence of operations 1. Enter the menu by typing the supervisor code.
Exit from the menu item 1. After finishing the setting, press the MENU button, to exit
Exit from the menu
20220103-V0
Synchronisation gate time
7.8.
Pulse width of the remote synchronisation signal. When the
active state of the synchron current is lower then this value
the instrument doesn't accept it as a synchronisation puls
(this function is useful for filtering false puls caused by
noise). The active state of the synchron current is high
(I > 12 mA). When the synchron current is in high state the
clock stops (you see
when goes to low state (I < 8 mA) the clock starts (you see
the time on the display).
The way the code should be type in is described in Chapter
7.1. Typing the code (password) in. You see on the

display:
.
2. Keep stepping by pressing the ▲ button as long as you
see this menu item:
3. Enter the menu item by pressing the ENTER button.
4. You see the actual gate time on the display, and the first
digit is blinking.
5. Pressing button ▲ button you can set the puls width from
1 to 8 seconds.
from the menu item, and you see this:
(2. If you want to change the setting you have done just
now, or if you just want to check what you have typed in, go
on with the operation from point 3 of the Sequence of
operations.)
(3. If you don't want to exit the menu, as you want to do
further settings, then you may select the desired menu
items by pressing the ▲ button.)
1. Press the MENU button. First the mnemonic
(Save), then the mnemonic
display. With this the storing of the settings is completed.
The instrument has exited the menu and goes on with the
measurement.
(06. menu item)

mnemonic on the display),

.

(Exit) are shown on the

.

31