Clearance.to.combustibles; Floor.protection - Regency Fireplace Products NARRABRI F100B-1 Owners & Installation Manual

Freestanding wood fire
Table of Contents

Advertisement

MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
DEFAULT OR FLOMET
SUPER SINGLE
A
650mm
B
225mm
C
375mm
D
0mm
E
135mm
F
300mm
G
760mm
H
780mm
Floor Protection
A combustible floor must be protected by non-combustible material (like
tile, concrete board, or as defined by local codes) extending beneath
the heater as follows;
From Side Top Plate Edge:
135mm
From Front:
From Back:
The floor protector should consist of 6mm thick compressed board sheet
which has a thermal conductivity of 0.08m
Tested with Flomet super single on a default kit incorporating 1 x 900mm.
180
solid backed decromesh casing.
o
Rear clearance 'B' can be reduced to 125mm by the addition of a 1 x 900mm x 180
spaced between the active flue and the decromesh.
The flue pipe shall extend not less than 4.6m above the top of the floor protector.
NOTE: Installation must be carried out by a licensed installer in accordance
with AS/NZS 2918:2001.
Regency Narrabri™ F100B-1 Freestanding Wood Fire
*(1)
300mm (In front of door opening)
0mm
.K/W.
2
stainless shield fitted and
o
installation