ABB ACS2000 AFE 2MVA User Manual page 98

Medium voltage drives
Table of Contents

Advertisement

CHAPTER 6 – ELECTRICAL INSTALLATION
Preparing cables for EMC plates
References
The orientation of the EMC plates is the same for
top and bottom cable entry: the sealing grommets
6-5 Preparing power
cables for EMC plates
face always upwards.
1. Remove the grommets.
2. To ensure proper sealing, cut along the marking
that corresponds to the cable diameter.
3. Slide the grommet onto the cable. The grom-
met must fit tightly to prevent water entering
the cabinet.
4. The grommets can be discarded if cables are
entered through the cabinet floor.
5. If necessary, remove the entry plate and push
the cable through the entry holes.
6. Prepare the cables as illustrated in 6-5.
-
-
1
A
2
3
4
6
7
8
6-5
(A) illustrates how cables with an outer cable
screen or shield are prepared
ing with the metal enclosure of the cabinet.
(B) illustrates how cables
without an outer
screen or shield
are
prepared.
B
5
for EMC bond-
Outer cable sheath
1
Grommet
2
Entry plate
3
EMC sleeve
4
Conductor insulation removed to expose
5
cable shield
Cable tie
6
Conductor screen extension to be
7
connected to PE ground busbar
Heat-shrinkable termination
8
98