Insulation tests
1.
All power cables to input transformer, between input transformer and drive, and from drive to motor mea-
sured, measured values within the required limits.
2.
Test report of the megger test available
If the test is carried out by the commissioning engineer of the drive, an
additional day per drive motor combination needs to be reserved.
After the test, the feeder cables can be connected, except at the drive
end. The test must comply with the specification.
Power supply
1.
Medium voltage available for the start-up of the drive
2.
Low voltage auxiliary power available for the start-up of the drive
Miscellaneous
1.
Sufficient number and correct type of spare parts are available
2.
Air conditioning of drive room ready for the load run of drive
3.
Optional equipment ready