ABB ACS2000 AFE 2MVA User Manual page 61

Medium voltage drives
Table of Contents

Advertisement

61
ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV. H
Table 3-7 Example for digital input signal allocation
Terminal
X11-1
X11-2
X11-3
X11-4
X11-5
X11-6
X11-7
X11-8
X11-9
X11-10
X12-1
X12-2
X12-3
X12-4
X12-5
X12-6
X12-7
X12-8
X12-9
X12-10
X13-1
X13-2
X13-3
X13-4
X13-5
X13-6
X13-7
X13-8
X13-9
X13-10
* Not configurable
Channel
Default setting
DI01
External start / stop request
Common
DI02
Forward / reverse
Common
DI03
Freely programmable
Common
DI04
Ramp 1 / 2
Common
DI05
Ext1 / Ext2
Common
DI06
Constant speed select
Common
DI07
External ON request (start DC link charge)
Common
DI08
Process stop (stops drive)
Common
DI09
MV switchgear open
Common
DI10
MV switchgear closed
Common
DI11
MV switchgear available (not tripped)
Common
DI12
Remote reset
Common
DI13
External OFF request
Common
DI14
Disable local operation
Common
+24 V
24 V control logic
+0 V
Common
Par. group
72.06 – 72.09
72.10 – 72.11
72.41 – 72.42
30 – 31
24 – 25
72.02 – 72.03
72.43 – 72.44
*
*
*
72.33 – 72.34
72.04 – 72.05
72.35 – 72.36