Communicator Call Direction Options; Software Reset Eeprom Memory To Factory Defaults; Through [42] Reserved For Future Use; Access Bypass Mask (Codes 1 To 8) - DSC PC3000 Installation Manual

Hide thumbs Also See for PC3000:
Table of Contents

Advertisement

Armed Status Indications
When the panel is established as a split system, and ONE
side only [Group A or B] is armed, the "Armed" indicator will
flash and the zone indicators for the group that has been
armed will flash.
If both Group A and Group B are armed the "Armed"
indicator will be on steadily and the zone lights will not flash.
Zone Bypassing Access Code
When the system is established for split arming, user zone
bypassing should be set so that bypassing requires the use
of an access code. (See section [19].)
Communicator
When the PC3000 is set up for "split arming" and both Group
A and Group B systems are reporting to the same telephone
number, Group A burglar alarms and restorals are
programmed as [1] in section [33] to call the 1st phone
number only. Light 7 in section [18] must be turned "ON".
Group B burglar alarms and restorals are programmed with
a [2] in Section [33] to call the 2nd phone number only. It is
necessary to program both the 1st and 2nd phone number
locations with the same telephone number.
Notes:
1. The following restrictions apply to split arming
applications:
• The Master Code must be assigned to side A and B.
• All codes and zones must be assigned even if not
used.
• Transmission delay must not be used.
• Home-away zones must not be used.
• The "One-Time Use" code must not be used.
• Exit Delay Termination must not be used. (section [60]
Light [7] OFF)
• Closing confirmation must not be used. (section [60]
Light [6] OFF)
• Quick Exit must not be used.
• Alarms displayed while armed must not be used.
• Audible Exit Fault must not be enabled.
2. PGM OUT Option A will work in a fully armed or fully
disarmed system.
3. Keyswitch arming will report with side A openings and
closings only.
[33] Communicator Call Direction
Options
Programming this section tells the dialer whether to send
transmissions to the 1st or 2nd telephone number.
There are four classes of dialer call direction options.
[0] No transmission for this group
[1] Call 1st phone number with back up to 2nd number
[2] Call 2nd phone number only
WWW.DIYALARMFORUM.COM
[3] Always call both phone numbers
Option [1] becomes "Call 1st number only" when item [7] in
section [18] is turned on (LIGHT ON). Do not program
backup to 2nd phone number in section [18] unless a 2nd
phone number is programmed.
After entering the section number, enter [0], [1], [2] or [3] for
each of the following reporting code groups in the order
given (total of six digits).
• Zone Group A Alarms and Restorals
• Zone Group B Alarms and Restorals
• Access Codes Group A Openings and Closings
• Access Codes Group B Openings and Closings
• Priority Alarms and Restorals
• Maintenance Alarms and Restorals
Where all reporting codes are to be sent to one telephone
number, enter [1] for all of the above groups.
[34] Software Reset EEPROM Memory to
Factory Defaults
This section is used to reset the EEPROM memory to the
original factory default values. As soon as [34] is entered the
EEPROM is reset and the program is restarted as though
power has just been applied.
Hardware Reset of EEPROM Memory to Factory Defaults
If the Installer's Code is lost through inadvertent
programming, the only means of reprogramming the system
is via a hardware reset. If the Installer's Lockout is enabled,
there is no way to reprogram the system without entering the
correct Installer's Code.
Follow the sequence outlined below to reset the panel to
factory default conditions.
1. Power unit down by removing both AC and battery power.
2. Using a short jumper, short pins marked "EEPROM
RESET" together.
3. Power PC3000 up.
4. Wait for 10 seconds. During this time the "Program" light
will flash.
5. Remove the shorting jumper.
6. The system will have reloaded the EEPROM with the
factory default codes.
[35] Through [42] Reserved for Future
Use

[43] Access Bypass Mask (Codes 1 to 8)

Use the same method of programming as used in section
[18]. In this section it is possible to control which users can
bypass zones. If the zone light is on, that user can bypass, if
that zone light is off, that user cannot bypass.
22