Section 4: Field Connections

SIGNALS

Safety Extra Low Voltage (SELV) Circuits
Connect only SELV circuits to the RIO-DIO, RIO-PUL, RIO-ANI or RIO-ANO modules.

RELAY CIRCUITS (OUTPUTS)

The Remote I/O Hub requires different relay modules to switch AC and DC loads. Please
check carefully that the load voltage matches the relay type fitted.
Model
# # # 0 # # # # # #
# # # 1 # # # # # #
# # # 2 # # # # # #
# # # 3 # # # # # #
# # # 4 # # # # # #
# # # 5 # # # # # #
# # # 6 # # # # # #
# # # 7 # # # # # #
Terminals 11 (13+) and 14 on each relay (RL1, RL2, RL3 & RL4) provide connections to the relays outputs,
controlled via the first RIO-DIO module, as follows:
The relay outputs can switch circuits designated as Installation Category III. Each relay output may switch a
maximum of 250VAC rms or 30VDC and is rated for 1 Amp resistive or inductive load at 60°C (140°F). All wiring
connected to any relay output must have a suitably sized protection device fitted to protect the relay circuit and
load being switched by it.
AC Relay
Output
AC LOAD
16
Crydom # CN024D24 = 24V DC Load Voltage @ 1 Amp Max.
Crydom # CN240A24 = 100-240V AC Load Voltage (50/60Hz) @ 1 Amp Max.
Relay Output / Load
RL1
RL2
RL3
AC
AC
AC
AC
AC
AC
AC
AC
DC
AC
AC
DC
AC
DC
AC
AC
DC
AC
AC
DC
DC
AC
DC
DC
Terminal
11 (13+)
14
F2
Fuse
11
14
1, 2, 3 or 4
InSpec Remote I/O HUB (ATEX, IECEx)
RL4
Model
# # # 8 # # # # # #
AC
DC
# # # 9 # # # # # #
AC
# # # A # # # # # #
DC
# # # B # # # # # #
AC
# # # C # # # # # #
DC
# # # D # # # # # #
AC
# # # E # # # # # #
DC
# # # F # # # # # #
# # # X # # # # # #
Duty
AC
DC
+
-
DC Relay
Output
DC LOAD
Relay Output / Load
RL1
RL2
RL3
RL4
DC
AC
AC
AC
DC
AC
AC
DC
DC
AC
DC
AC
DC
AC
DC
DC
DC
DC
AC
AC
DC
DC
AC
DC
DC
DC
DC
AC
DC
DC
DC
DC
No relays fitted
F3
Fuse
11
14
5, 6, 7 or 8