Troubleshooting; Unit Will Not Start Or Starts Then Stops; Unit Operates Long Or Continuously In Cooling - Carrier 69NT40-541-001 Operation And Service

Container refrigeration units
Table of Contents

Advertisement

CONDITION
6.1

UNIT WILL NOT START OR STARTS THEN STOPS

External power source OFF
Start-Stop switch OFF or defective
No power to unit
Circuit breaker tripped or OFF
Autotransformer not connected
Circuit breaker OFF or defective
Control transformer defective
Loss of control power
Fuses (F3A, F3B) blown
Start-Stop switch OFF or defective
Evaporator fan motor internal protector open
Condenser fan motor internal protector open
Component(s) Not Op-
Compressor internal protector open
erating
High pressure switch open
Heat termination thermostat open
Low line voltage
Single phasing
Compressor hums, but
does not start
Shorted or grounded motor windings
Compressor seized
6.2

UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING

Hot load (Failure to Pre-cool)
Container
Defective box insulation or air leak
Shortage of refrigerant
Evaporator coil covered with ice
Evaporator coil plugged with debris
Evaporator fan(s) rotating backwards
Defective evaporator fan motor/capacitor
Air bypass around evaporator coil
Refrigeration System
Controller set too low
Compressor service valves or liquid line shutoff valve partially closed
Dirty condenser
Compressor worn
Current limit (function code Cd32) set to wrong value
Suction modulation valve malfunction
SECTION 6

TROUBLESHOOTING

POSSIBLE CAUSE
6–1
REMEDY /
REFERENCE
Turn on
Check
Check
5.2.2
Check
Replace
Check
Check
7.16
7.11
7.8
6.7
Replace
Check
Check
7.8
7.8
Normal
Repair
7.7.1
6.6
7.15
7.15/
7.16
7.17
Check
Reset
Open valves
completely
7.10
7.8
4.3.5
7.18
T-316