Table 4-8 Datacorder Function Code Assignments - Carrier 69NT40-541-001 Operation And Service

Container refrigeration units
Table of Contents

Advertisement

CODE #
TITLE
Recorder Supply
dC1
Temperature
Recorder Return
dC2
Temperature
USDA 1,2,3
dC3-5
Temperatures
Network Data
dC6-13
Points 1-8
Cargo Probe 4
dC14
Temperature
dC15-19 Future Expansion
Temperature Sen-
dC20-24
sors 1-5 Calibration
dC25
Future Expansion
dC26,27 S/N, Left 4, Right 4
dC28
Minimum Days Left
dC29
Days Stored
dC30
Date of last Trip start
dC31
Battery Test
dC32
Time: Hour, Minute
dC33
Date: Month, Day
dC34
Date: Year
Cargo Probe 4
dC35
Calibration
T-316
Table 4–8 DataCORDER Function Code Assignments
Inapplicable Functions Display "-----"
To Access: Press ALT. MODE key
Current reading of the supply recorder sensor.
Current reading of the return recorder sensor.
Current readings of the three USDA probes.
Current values of the network data points (as configured). Data point 1 (Code
6) is generally the humidity sensor and its value is obtained from the Controller
once every minute.
Current reading of the cargo probe #4.
These codes are for future expansion, and are not in use at this time.
Current calibration offset values for each of the five probes: supply, return,
USDA #1, #2, and #3. These values are entered via the interrogation program.
This code is for future expansion, and is not in use at this time.
The DataCORDER serial number consists of eight characters. Function code
dC26 contains the first four characters. Function code dC27 contains the last
four characters. (This serial number is the same as the Controller serial number)
An approximation of the number of logging days remaining until the
DataCORDER starts to overwrite the existing data.
Number of days of data that are currently stored in the DataCORDER.
The date when a Trip Start was initiated by the user. In addition, if the system
goes without power for seven continuous days or longer, a trip start will auto-
matically be generated on the next AC power up.
Shows the current status of the optional battery pack.
PASS: Battery pack is fully charged.
FAIL: Battery pack voltage is low.
Current time on the real time clock (RTC) in the DataCORDER.
Current date (month and day) on the RTC in the DataCORDER.
Current year on the RTC in the DataCORDER.
Current calibration value for the Cargo Probe. This value is an input via the in-
terrogation program.
DESCRIPTION
NOTE
4–32