ENSURE THAT THE POWER CORD TO THE MACHINE HAS
BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE
SERVICE. THE SERVICING AND REPAIR OF THIS UNIT
SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
Removal of the cover is achieved by means of four screws at the sides of the
unit at base level. With the cover removed all maintenance can be carried out.
1.
Clean the surface of the evaporator and condenser coils by
blowing the dirt out from behind the fins with compressed air.
Hold the nozzle of the air hose away from the coil (approx 6") to
avoid damaging the fins. Alternatively, vacuum clean the coils.
DO NOT STEAM CLEAN REFRIGERATION COILS
2.
Check that the fan is firmly secured to the motor shaft and that the
fan rotates freely.
THE FAN IS SEALED FOR LIFE AND DOES NOT NEED LUBRICATING.
3.
To check the refrigerant charge, run the unit for 20 minutes (with
humidistat set to maximum) and briefly remove the cover. The
evaporator coil should be evenly frost coated across its surface. At
temperatures above 25°C, the coil may be covered with droplets of
water rather than frost. Partial frosting accompanied by frosting of
the thin capillary tubes, indicates loss of refrigerant gas or low
charge.
4.
Check all wiring connections.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
S
C
ERVICE
ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO

ROUTINE SERVICE

WARNING:
PERSON.
WARNING:
PREVENT PERMANENT DAMAGE
Page 7 of 12
Drawing : - TPC385
Issue
: - 4
Date
: - 24/11/16
,
E
CONTACT THE
BAC
.