Routine Service - EIP RM4500 Owner's Manual

Industrial dehumidifier
Table of Contents

Advertisement

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN
DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE.
THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE
CARRIED OUT BY A SUITABLY QUALIFIED PERSON.
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
1.
Clean the surface of the evaporator and condenser coils by blowing
the dirt out from behind the fins with compressed air. Hold the
nozzle of the air hose away from the coil to avoid damaging the fins.
Alternatively, vacuum clean the coils.
DO NOT STEAM CLEAN REFRIGERATION COILS
2.
Check that the fan rotates freely. The fan motor is sealed for life
and therefore does not need oiling.
3.
To check the refrigerant charge remove front cover and run the unit
for 15 minutes and observe the evaporator coil. It should be evenly
coated with frost across its surface. At temperatures above 25°C,
the coil may be covered with droplets of water rather than frost.
Partial frosting accompanied by frosting of the thin capillary tubes,
indicates loss of refrigerant gas or low charge.
4.
Check all wiring connections, including mains cable for damage or
loose connections.
5.
In order to check the defrost operation, the unit needs to be
operated in an ambient temperature of less than 15° C for at least
20mins. When operated In this condition the unit should defrost at
least once every hour. The defrost mode can be monitored by
observing the ice melting on the coil face, prior to defrost the face
will show a white coating of frost, which should clear during defrost
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
S
C
ERVICE
ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO

ROUTINE SERVICE

WARNING:
WARNING:
PREVENT PERMANENT DAMAGE
Page 6 of 12