Daikin FXFN50A2VEB Installer And User Reference Manual page 75

Co₂ conveni-pack: indoor unit
Table of Contents

Advertisement

(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number / C1: First code number
• —: Value number / C2: Second code number
: Default
(2)
Fan speed:
• LL: Low fan speed (set during thermostat OFF)
• L: Low fan speed (set by the user interface)
• H: High fan speed
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2, 3: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by LL (Monitoring 1), by L
(Monitoring 2) or by H (Monitoring 3).
FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P677925-1 – 2021.07
If the ... decoration panel is used
Standard or self-cleaning
Design
Setting: Airflow direction range
This setting must correspond with the needs of the user.
If you want set the airflow direction range to...
Upper
Medium
Lower
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It determines the fan
speed of the indoor unit during thermostat OFF condition.
1 If you have set the fan to operate, set the air volume speed:
If you want...
During thermostat
OFF at cooling
operation
During thermostat
OFF at heating
operation
(2)
LL
(2)
Setup volume
(a)
OFF
(2)
Monitoring 1
(2)
Monitoring 2
(2)
Monitoring 3
(2)
H
(2)
LL
(2)
Setup volume
(a)
OFF
(2)
Monitoring 1
(2)
Monitoring 2
(2)
Monitoring 3
(2)
H
20
Configuration
|
(1)
Then
M
SW/C1
—/C2
13 (23)
15
01
02
(1)
Then
M
SW/C1
—/C2
13 (23)
4
01
02
03
(1)
Then
M
SW/C1
—/C2
12 (22)
6
01
02
03
04
05
06
07
12 (22)
3
01
02
03
04
05
06
07
Installer and user reference guide