Daikin FXFN50A2VEB Installer And User Reference Manual page 49

Co₂ conveni-pack: indoor unit
Table of Contents

Advertisement

FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P677925-1 – 2021.07
c 3-way air flow (optional blocking pad kit required)
Ceiling insulation. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10 mm thickness, polyethylene foam).
Spacing. Mind the following requirements:
a
A
A Minimum distance to the wall (see below)
B Minimum and maximum distance to the floor (see below)
C 50~71 class:
≥269 mm: In case of installation with standard decoration panel
≥311 mm: In case of installation with design decoration panel
≥349 mm: In case of installation with self-cleaning decoration panel
≥319 mm: In case of installation with standard panel + fresh air intake kit
≥361 mm: In case of installation with design panel + fresh air intake kit
112 class:
≥311 mm: In case of installation with standard decoration panel
≥353 mm: In case of installation with design decoration panel
≥391 mm: In case of installation with self-cleaning decoration panel
≥361 mm: In case of installation with standard panel + fresh air intake kit
≥403 mm: In case of installation with design panel + fresh air intake kit
a Indoor unit
b Lighting (the figure shows ceiling-mounted lighting, but recessed lighting is also
allowed)
c Air fan
d Static volume (example: table)
A: Minimum distance to the wall. Depends on the air flow directions towards
the wall.
a
≥1500
A
a Air outlet and corners open
b Air outlet closed, corners open (optional blocking pad kit required)
c Air outlet and corners closed (optional blocking pad kit required)
B: Minimum and maximum distance to the floor:
-
Minimum: 2.7 m to avoid accidental touching.
-
Maximum: Depends on the airflow directions and the capacity class. See
"20.1 Field
setting" [
INFORMATION
Maximum distance to the floor for the 3-way and the 4-way airflow (which require an
optional blocking pad kit) may differ. See the installation manual of the optional
blocking pad kit.
INFORMATION
Some options may require additional service space. Refer to the installation manual
of the used option before installation.
b
c
≥1500
≥2000
≥4000
b
≥500
A
4
 74].
16
Unit installation
|
a
d
(mm)
c
≥200
A
Installer and user reference guide
49