Table of contents Table of contents 1 About the documentation About this document ..............................2 General safety precautions About the documentation .............................. 2.1.1 Meaning of warnings and symbols ........................ For the installer ................................2.2.1 General ................................2.2.2 Installation site ............................... 2.2.3 Refrigerant —...
Page 3
Table of contents For the installer 14 About the box 14.1 Indoor unit ..................................42 14.1.1 To unpack and handle the unit ........................42 14.1.2 To remove the accessories from the indoor unit ..................42 15 About the units and options 15.1 Identification ...................................
The original documentation is written in English. All other languages are translations. Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
General safety precautions 2 General safety precautions 2.1 About the documentation ▪ The original documentation is written in English. All other languages are translations. ▪ The precautions described in this document cover very important topics, follow them carefully. ▪ The installation of the system, and all activities described in the installation manual and in the installer reference guide MUST be performed by an authorised installer.
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
General safety precautions WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire. CAUTION Do NOT touch the air inlet or aluminium fins of the unit. CAUTION ▪...
Page 8
General safety precautions NOTICE Make sure the field piping and connections are NOT subjected to stress. WARNING During tests, NEVER pressurise the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit). WARNING Take sufficient precautions in case of refrigerant leakage.
General safety precautions CAUTION When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount. 2.2.4 Electrical DANGER: RISK OF ELECTROCUTION ▪...
Page 10
General safety precautions NOTICE Precautions when laying power wiring: ▪ Do NOT connect wiring of different thicknesses to the power terminal block (slack in the power wiring may cause abnormal heat). ▪ When connecting wiring which is the same thickness, do as shown in the figure above.
WARNING Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
Page 12
Specific installer safety instructions WARNING When using safety shut-off valves, make sure to install measures such as a bypassing piping with a pressure relief valve (from liquid pipe to gas pipe). When the safety shut-off valves close and no measures are installed, increased pressure may damage the liquid piping.
Page 13
Specific installer safety instructions WARNING If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. Commissioning (see "19 Commissioning" [ 72]) WARNING If the panels on the indoor units are not installed yet, make sure to power OFF the system after finishing the test run.
User safety instructions 4 User safety instructions Always observe the following safety instructions and regulations. 4.1 General WARNING If you are NOT sure how to operate the unit, contact your installer. WARNING This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning...
User safety instructions ▪ Units are marked with the following symbol: This means that electrical and electronic products may NOT be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts MUST be done by an authorised installer and MUST comply with applicable legislation.
Page 17
User safety instructions CAUTION ▪ NEVER touch the internal parts of the controller. ▪ Do NOT remove the front panel. Some parts inside are dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer. WARNING This unit contains electrical and hot parts.
Page 18
User safety instructions WARNING Do NOT place a flammable spray bottle near the air conditioner and do NOT use sprays near the unit. Doing so may result in a fire. Maintenance and service (see "10 Maintenance and service" [ 29]) WARNING: System contains refrigerant under very high pressure.
Page 19
User safety instructions "10.5 About the refrigerant" [ 33]) About the refrigerant (see WARNING ▪ Do NOT pierce or burn refrigerant cycle parts. ▪ Be aware that the refrigerant inside the system is odourless. WARNING The R744 refrigerant (CO ) inside the unit is odourless, non-flammable and normally does NOT leak.
About the system 5 About the system NOTICE The appliance shall be stored so as to prevent mechanical damage. WARNING Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire. Contact your dealer. NOTICE Do NOT use the system for other purposes.
Page 21
About the system a Main outdoor unit (LRYEN10*) b Capacity up unit (LRNUN5*) c Communication box (BRR9B1V1) d BEV2 unit e Indoor unit for air conditioning f Indoor unit for refrigeration (showcase) g Indoor unit for refrigeration (blower coil) h Safety valve i CO control panel j CO...
Total electric power input elec Sound power level (cooling) dB(A) Sound power level (heating) dB(A) Contact details: DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody 1/1155, 301 00 Plzeň Skvrňany, Czech Republic FXFN50A FXFN71A FXFN112A FXFN50~112A2VEB Installer and user reference guide CO₂...
User interface 6 User interface CAUTION ▪ NEVER touch the internal parts of the controller. ▪ Do NOT remove the front panel. Some parts inside are dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
Before operation 7 Before operation WARNING This unit contains electrical parts. WARNING Before operating the unit, be sure the installation has been carried out correctly by an installer. CAUTION It is unhealthy to expose your body to the air flow for a long time. CAUTION To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
Operation 8 Operation 8.1 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation. Cooling and drying Heating Outdoor unit –5~43°C DB –20~16°C WB Indoor unit 14~24°C WB 15~27°C DB Indoor humidity ≤80% — To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.
Operation Icon Operation mode Auto. In Auto mode, the indoor unit automatically switches between heating and cooling mode, as required by the setpoint. 8.2.2 Special heating operation modes Operation Description Defrost To prevent a loss of heating capacity due to frost accumulation in the outdoor unit, the system will automatically switch to defrost operation.
Operation INFORMATION Depending on system layout and organisation, Auto airflow direction may not be available. INFORMATION For setting procedure of the airflow direction, see the reference guide or the manual of the used user interface. Automatic airflow control In the following operating conditions, the airflow direction of the indoor units is controlled automatically: ▪...
Energy saving and optimum operation 9 Energy saving and optimum operation CAUTION NEVER expose little children, plants or animals directly to the airflow. NOTICE Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
Maintenance and service 10 Maintenance and service 10.1 Precautions for maintenance and service WARNING: System contains refrigerant under very high pressure. The system MUST be serviced by qualified persons ONLY. NOTICE Maintenance MUST be done by an authorised installer or service agent. We recommend performing maintenance at least once a year.
Maintenance and service DANGER: RISK OF ELECTROCUTION To clean the air conditioner or air filter, be sure to stop operation and turn all power supplies OFF. Otherwise, an electrical shock and injury may result. WARNING Be careful with ladders when working in high places. Following symbols may occur on the indoor unit: Symbol Explanation...
Maintenance and service Design panel: 2 Remove the air filter. Standard panel: Design panel: 3 Clean the air filter. Use a vacuum cleaner or wash with water. If the air filter is very dirty, use a soft brush and neutral detergent. 4 Dry the air filter in the shadow.
Maintenance and service Standard panel: Design panel: 2 Remove the suction grille. Standard panel: 45° Design panel: 3 Remove the air filter. 4 Clean the suction grille. Wash with a soft bristle brush, and water or neutral detergent. If the suction grille is very dirty, use a typical kitchen cleaner, leave it on for 10 min, then wash it with water.
Maintenance and service NOTICE ▪ Do NOT use gasoline, benzene, thinner polishing powder or liquid insecticide. Possible consequence: Discoloration and deformation. ▪ Do NOT use water or air of 50°C or higher. Possible consequence: Discoloration and deformation. ▪ Do NOT scrub firmly when washing the blade with water. Possible consequence: The surface sealing peels off.
Maintenance and service WARNING The R744 refrigerant (CO ) inside the unit is odourless, non-flammable and normally does NOT leak. ALWAYS install a CO detector according to the specifications of standard EN378. If the refrigerant leaks in high concentrations in the room, it may have negative effects on its occupants such as asphyxiation and carbon dioxide poisoning.
Troubleshooting 11 Troubleshooting If one of the following malfunctions occur, take the measures shown below and contact your dealer. WARNING Stop operation and shut OFF the power if anything unusual occurs (burning smells etc.). Leaving the unit running under such circumstances may cause breakage, electrical shock or fire.
Troubleshooting Malfunction Measure The system operates but ▪ Check if air inlet or outlet of outdoor or indoor cooling or heating is unit is not blocked by obstacles. Remove any insufficient. obstacles and make sure the air can flow freely. ▪...
Troubleshooting 11.1.4 Symptom: White mist comes out of a unit (Indoor unit) ▪ When humidity is high during cooling operation. If the interior of an indoor unit is extremely contaminated, the temperature distribution inside a room becomes uneven. It is necessary to clean the interior of the indoor unit. Ask your dealer for details on cleaning the unit.
Troubleshooting 11.1.11 Symptom: In winter, indoor unit generates cold air and fan is turned ON regardless of setting The system went to defrost operation. The fan of the indoor unit is turned ON for correct defrost operation, cold air may be generated during this time period. FXFN50~112A2VEB Installer and user reference guide CO₂...
Relocation 12 Relocation Contact your dealer for removing and reinstalling the total unit. Moving units requires technical expertise. FXFN50~112A2VEB Installer and user reference guide CO₂ Conveni-Pack: indoor unit 4P677925-1 – 2021.07...
Disposal 13 Disposal NOTICE Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. FXFN50~112A2VEB Installer and user reference guide CO₂...
About the box 14 About the box 14.1 Indoor unit 14.1.1 To unpack and handle the unit Use a sling of soft material or protective plates together with a rope when lifting the unit in order to avoid damage or scratches to the unit. 1 Lift the unit by holding on to the hanger brackets without exerting any pressure on other parts, especially on refrigerant piping, drain piping and other resin parts.
Page 43
About the box h Metal clamp i Sealing pads: Large (drain pipe), medium 1 (gas pipe), medium 2 (liquid pipe), small (electrical wiring) j Drain hose k Power supply cable l Communication cable m Insulation piece: Small (liquid pipe) n Insulation piece: Large (gas pipe) o Insulation piece (drain pipe) FXFN50~112A2VEB Installer and user reference guide...
About the units and options 15 About the units and options In this chapter 15.1 Identification................................... 15.1.1 Identification label: Indoor unit ..........................15.2 About the indoor unit................................15.3 System layout..................................15.4 Combining units and options..............................15.4.1 Possible options for the indoor unit ........................15.1 Identification NOTICE When installing or servicing several units at the same time, make sure NOT to switch...
About the units and options a Main outdoor unit (LRYEN10*) b Capacity up unit (LRNUN5*) c Communication box (BRR9B1V1) d BEV2 unit e Indoor unit for air conditioning f Indoor unit for refrigeration (showcase) g Indoor unit for refrigeration (blower coil) h Safety valve i CO control panel...
About the units and options 15.4.1 Possible options for the indoor unit Make sure you have the following mandatory options: ▪ User interface: Wired or wireless (refer to catalogues and technical literature to select a suitable user interface) INFORMATION Madoka with buzzer is a recommended option. In case you use another user interface, an additional safety alarm in combination with a gas detection device (field supply) may be required;...
Unit installation 16 Unit installation WARNING Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard. WARNING ▪ Make sure to install all necessary countermeasures in case of refrigerant leakage according to standard EN378 (see "16.1.2 ...
Page 48
Unit installation It is NOT recommended to install the unit in the following places because it may shorten the life of the unit: ▪ Where the voltage fluctuates a lot ▪ In vehicles or vessels ▪ Where acidic or alkaline vapour is present NOTICE This is a class A product.
Page 49
Unit installation c 3-way air flow (optional blocking pad kit required) ▪ Ceiling insulation. When conditions in the ceiling exceed 30°C and a relative humidity of 80%, or when fresh air is inducted into the ceiling, then additional insulation is required (minimum 10 mm thickness, polyethylene foam). ▪...
Unit installation 16.1.2 Additional installation site requirements for CO₂ refrigerant WARNING In case of mechanical ventilation, take care the ventilated air is exhausted to the outdoor space and NOT into another closed area. Refrigerant basic characteristics Refrigerant R744 RCL (refrigerant concentration limit) 0.072 kg/m QLMV (quantity limit with minimum ventilation) 0.074 kg/m...
Page 51
Unit installation 16‒1 Description of access categories Access category Description Examples General access Rooms, parts of buildings, buildings Hospitals, courts or prisons, theatres, where: supermarkets, schools, lecture halls, public transport terminals, hotels, restaurants. ▪ sleeping facilities are provided; ▪ people restricted their movements;...
Page 52
Unit installation ▪ safety shut-off valves ▪ safety alarm, in combination with a CO refrigerant leak detector (a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements) ▪ refrigerant leak detector WARNING Install the unit ONLY in locations where the doors of the occupied space are NOT tight fitting.
Page 53
Unit installation Example: Total refrigerant charge in the system is 45 kg and room volume is 300 m . 45/300=0.15, which is >QLMV (0.074) and <QLAV (0.18), therefore install at least 1 appropriate measure in the room. QLAV QLMV 100 150 200 250 300 350 600 650 700 750 800 850 900 950 1000 B (m³)
Unit installation b 2 appropriate measures required c 1 appropriate measure required d No measure required INFORMATION Even if there is no refrigerating system on the lowest floor, where the largest system charge (kg) in the building divided by total volume of the lowest floor (m ) exceed the value for QLMV, provide a mechanical ventilation in accordance with EN 378-3:2016.
Page 55
Unit installation NOTICE After installing the decoration panel: ▪ Make sure there is no gap between the unit body and the decoration panel. Possible consequence: Air might leak and cause dew drop. ▪ Make sure no oil remains on the plastic parts of the decoration panel. Possible consequence: Degradation and damage of plastic parts.
Page 56
Unit installation ▪ Ceiling opening and unit: Make sure the ceiling opening is within the following limits: Minimum: 860 mm to be able to fit the unit. Maximum: 910 mm to ensure enough overlap between the decoration panel and the suspended ceiling. If the ceiling opening is larger, add extra ceiling material.
Unit installation D In case of installation with design decoration panel a Suspended ceiling b Installation guide (accessory) c Unit ▪ Level. Make sure the unit is level at all 4 corners using a level or a water-filled vinyl tube. a Level b Vinyl tube c Water level...
Page 58
Unit installation ≤300 1000~1500 (mm) a Metal clamp (accessory) b Drain hose (accessory) c Rising drain piping (vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter) (field supply) d Hanging bars (field supply) ▪ Combining drain pipes. You can combine drain pipes. Make sure to use drain pipes and T-joints with a correct gauge for the operating capacity of the units.
Page 59
Unit installation b Drain hose (accessory) c Metal clamp (accessory) d Large sealing pad (accessory) e Insulation piece (drain pipe) (accessory) f Drain piping (field supply) To check for water leaks The procedure differs depending on whether installation of the system is already completed.
Page 60
Unit installation e Drain pipe 5 Turn OFF the power. 6 Disconnect the electrical wiring. ▪ Remove the service cover. ▪ Disconnect the power supply. ▪ Disconnect the user interface. ▪ Reattach the service cover. When installation of the system is already completed 1 Start cooling operation (see the reference guide or the service manual of the user interface).
Piping installation 17 Piping installation In this chapter 17.1 Preparing refrigerant piping ..............................17.1.1 Refrigerant piping requirements ........................... 17.1.2 Refrigerant piping insulation..........................17.2 Connecting the refrigerant piping............................17.2.1 About connecting the refrigerant piping....................... 17.2.2 Precautions when connecting the refrigerant piping.................... 17.2.3 Guidelines when connecting the refrigerant piping....................
Piping installation Refrigerant piping material ▪ Piping material: K65 copper-iron alloy (CuFe2P), maximum operating pressure = 120 bar ▪ Piping temper grade and thickness: Outer diameter (Ø) Temper grade Thickness (t) Ø 9.5 mm (3/8") R420 ≥0.65 mm (drawn) 12.7 mm (1/2") ≥0.85 mm Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High"...
Piping installation 17.2.2 Precautions when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters: ▪ "2 General safety precautions" [ 5] ▪ "17.1 Preparing refrigerant piping" [ 61] DANGER: RISK OF BURNING/SCALDING CAUTION NEVER bend high pressure piping! Bending can reduce the pipe thickness and thus weaken the piping.
Piping installation ▪ Set the nitrogen pressure to 20 kPa (0.2 bar) (just enough so it can be felt on the skin) with a pressure-reducing valve. a Refrigerant piping b Part to be brazed c Taping d Manual valve e Pressure-reducing valve f Nitrogen ▪...
Page 65
Piping installation a Field piping b Brazed connection c Piping on the indoor unit side d Plastic hold plate e Insulation attached on the unit 3 Insulate the refrigerant piping on the indoor unit as follows: A Liquid piping B Gas piping a Insulation material (field supply) b Tie wraps (accessory) c Insulation pieces: Large (gas pipe), small (liquid pipe) (accessory)
Electrical installation 18 Electrical installation NOTICE This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. In this chapter 18.1 About connecting the electrical wiring ..........................18.1.1 Precautions when connecting the electrical wiring ....................
Electrical installation WARNING ▪ If the power supply has a missing or wrong N-phase, equipment might break down. ▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock. ▪...
Electrical installation 18.2 To connect the electrical wiring to the indoor unit NOTICE ▪ Follow the wiring diagram (delivered with the unit, located at the inside of the service cover). ▪ For instructions on how to connect the optional equipment, see the installation manual delivered with the optional equipment.
Page 70
Electrical installation 10~15 70~90 (mm) a Service cover (with wiring diagram) b Opening for cables c Connection of power supply d Tie wrap e Connection of user interface and transmission cable Complete system example ▪ Example: 1 user interface controls 1 indoor unit. Control box IN/D OUT/D a Outdoor unit...
Electrical installation ▪ Setting master unit (Cooling/Heating masterhood). In case of group control, connect the user interface wiring directly to the master unit. Do not connect user interfaces directly to slave units. Slave units are restricted in their operation by the master unit (e.g.
19 Commissioning NOTICE General commissioning checklist. Next to the commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required). The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during the commissioning and hand-over to the user.
Commissioning WARNING If the panels on the indoor units are not installed yet, make sure to power OFF the system after finishing the test run. To do so, turn OFF operation via the user interface. Do NOT stop operation by turning OFF the circuit breakers. 19.3 Checklist before commissioning 1 After the installation of the unit, check the items listed below.
Configuration 20 Configuration 20.1 Field setting Make the following field settings so that they correspond with the actual installation setup and with the needs of the user: ▪ Ceiling height ▪ Decoration panel type ▪ Air flow direction range ▪ Air volume when thermostat control is OFF ▪...
Page 75
Configuration If the … decoration panel is used Then SW/C1 —/C2 Standard or self-cleaning 13 (23) Design Setting: Airflow direction range This setting must correspond with the needs of the user. If you want set the airflow direction range to… Then SW/C1 —/C2...
Page 76
Configuration Only use in combination with optional remote sensor or when setting M 10 (20), SW/C1 2, —/C2 3 is used. Setting: Time to clean air filter This setting must correspond with the air contamination in the room. It determines the interval at which "Time to clean filter"...
Page 77
Configuration If you want to set… Then Example SW/C1 —/C2 0°C 12 (22) cooling 24°C/heating 24°C 1°C cooling 24°C/heating 23°C 2°C cooling 24°C/heating 22°C 3°C cooling 24°C/heating 21°C 4°C cooling 24°C/heating 20°C 5°C cooling 24°C/heating 19°C 6°C cooling 24°C/heating 18°C 7°C cooling 24°C/heating 17°C Setting: Auto-restart after power failure...
Hand-over to the user 21 Hand-over to the user Once the test run is finished and the unit operates properly, please make sure the following is clear for the user: ▪ Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
Troubleshooting 22 Troubleshooting 22.1 Solving problems based on error codes If the unit runs into a problem, the user interface displays an error code. It is important to understand the problem and to take measures before resetting an error code. This should be done by a licensed installer or by your local dealer. This chapter gives you an overview of most possible error codes and their descriptions as they appear on the user interface.
Disposal 23 Disposal NOTICE Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. FXFN50~112A2VEB Installer and user reference guide CO₂...
Technical data 24 Technical data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 24.1 Wiring diagram 24.1.1 Unified wiring diagram legend...
Page 82
Technical data Symbol Meaning AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*, Connection, connector MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE D*, V*D Diode Diode bridge DIP switch Heater FU*, F*U, (for characteristics, refer to Fuse PCB inside your unit) Connector (frame ground) Harness H*P, LED*, V*L...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Page 88
4P677925-1 2021.07 Verantwortung für Energie und Umwelt...