Daikin FXFN50A2VEB Installer And User Reference Manual page 58

Co₂ conveni-pack: indoor unit
Table of Contents

Advertisement

16
|
Unit installation
To connect the drain piping to the indoor unit
Installer and user reference guide
58
a
b
a Metal clamp (accessory)
b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter) (field supply)
d Hanging bars (field supply)
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with a correct gauge for the operating capacity of the units.
a T-joint
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4  mm from the
metal clamp part.
3 Check for water leaks (see
4 Install the insulation piece (drain pipe).
5 Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps.
6 Connect the drain piping to the drain hose.