● Drain Pipe Joint
Drain pipe joint is a drain connection device when using
outdoor unit chassis as a water tray.
Drain pipe connection components:
Model
Part Name
Drain pipe joint
DC-01Q
Drain pipe cap
Rubber cap
Installation location
For example, JVOH140VPEMBQ models:
Drain pipe
field supply

6. The Refrigerant Piping Construction

● Refrigerant R410A is used in the refrigerant circulation system. Do not allow oxygen, acetylene
or other flammable and toxic gases to fill the refrigerant pipe during leakage and air tightness
test. These gases are very dangerous and may cause an explosion. It is recommended to use
nitrogen.
● Ensure that there is no pressure inside the stop valve when removing the cap on the stop
valve.
Make sure that the refrigerant piping is connected in the same refrigeration system.

6.1 Piping Material

(1) Prepare copper pipe for on-site construction.
(2) Follow the instructions in Table 6.1 and Table 6.2. Select the copper pipe specifications.
(3) Choose clean copper pipes. Make sure that there is no dust and moisture inside the copper pipe
inner wall. Before performing piping connection, use dry air or nitrogen to blow the inside of the
copper pipe to remove internal dust or impurities. Do not cut the copper pipe with tools such as
saws and grinding wheels that can produce metal debris.
Material / Color
PP / black
PP / black
CR / black
Drain cap position (2 places)
Drain pipe connection
position (2 places)
DANGER
!
CAUTION
!
Name
Drain pipe joint
Quantity
1
Connect the drain connection
1
Blocking the water pipe mouth
4
Sealed drain connection and drain cap
Rear
19
Model
DC-01Q
Usage
Side view
Front
Chassis
Drain cap
Drain pipe
connection