Checking The Gas Train Filter Element - Viessmann MatriX-Disk burner Service Instructions For Contractors

Burner for natural gas e and ll
Table of Contents

Advertisement

Checking the gas train valves for tightness
6. After completing the test, close the screw on test
connector
B
. Check the test connector for leaks.
Danger
Escaping gas leads to a risk of explosion.
Check the test connector for gas tightness.
!
Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into
contact with electrical contacts.
Note
Only use suitable and approved leak detection
agents (EN 14291) and devices for the tightness
test. Leak detection agents with unsuitable constit-
uents (e.g. nitrides, sulphides) can cause material
damage.
Remove residues of the leak detection agent after
testing.

Checking the gas train filter element

Fig. 21
Commissioning, inspection, maintenance
(cont.)
1. Determine the pressure differential across the gas
filter. For this, determine the pressure differential
between test connectors
tion at the upper heating output. See Fig.20 on
page 26.
If
p > 10 mbar, clean the filter.
Δ
2. Cleaning the filter
Close the gas shut-off valve. Unscrew inlet flange
from the gas train.
3. Undo screws, remove the filter.
4. Carefully clean the filter with compressed air. If
necessary, replace the filter.
5. Reassemble the gas train in reverse order using
new gaskets.