Reducing The Maximum Heating Output (If Required) - Viessmann MatriX-Disk burner Service Instructions For Contractors

Burner for natural gas e and ll
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Reducing the maximum heating output (if required)

The maximum heating output of the burner can be
reduced if required.
Programming unit on the burner control unit
Status
Service
R
S
Fig. 5
Press the following buttons:
1. Press and hold S for longer than 2 s,
2.
repeatedly, until "6" is shown under "Service".
3. S to confirm, "6" is shown under "Status" and "1" is
shown under "Service".
14
4. S to confirm, "1" is shown under "Status". The cur-
rent value for the maximum heating output in % is
shown under "Service".
5. Use
or
output.
6. S to confirm. If adopted successfully, "1" is shown
under "Service"; if it failed, "0" will appear.
7. S to change to the operating display.
8. R, the system will be restarted.
Note
Max. heating output can also be reduced via the
flashes.
Vitotronic control unit.
Vitotronic control unit operating instructions
to select the required maximum heating