Commissioning The Burner - Viessmann MatriX-Disk burner Service Instructions For Contractors

Burner for natural gas e and ll
Table of Contents

Advertisement

Commissioning the burner

Danger
CO build-up as a result of incorrect burner
adjustment or flue gas system leakage can have
serious health implications.
Always carry out a CO test before and after
work on gas appliances.
!
Please note
Dust can impair the function of the burner and
falsify burner settings.
Only operate the burner with the air filter instal-
led.
A
Fig. 4
Commissioning, inspection, maintenance
Vitotronic control unit operating instructions
and service instructions
Neutralising system operating instructions
Flue system installation instructions
"Vitocrossal, type CRU" service instructions
1. Check the heating system pressure.
"Vitocrossal, type CRU" service instructions
2. For open flue operation: Check that the ventilation
facility in the installation room complies with the
boiler room guidelines.
3. Open the gas line shut-off valves.
4. Check the static pressure. See page 15.
5. Check the adjustment on air pressure switch 1
for the specified set pressure.
Rated heating output
800 kW
1000 kW
6. Switch ON the mains isolator (outside the installa-
tion room).
7. Switch on the ON/OFF switch at the programming
unit of the Vitotronic control unit.
Vitotronic control unit operating instructions
Note
During commissioning, the appliance may enter a
fault state due to remaining airlocks in the gas line:
"Burner fault" and
Purge the gas line again.
Confirming the fault on the display of the
Vitotronic control unit resets the burner.
8. Check all gaskets and plugs, and retighten if nec-
essary.
A
2 mbar (0.2 kPa)
4 mbar (0.4 kPa)
are shown on the display
13