Viessmann MatriX-Disk burner Service Instructions For Contractors page 42

Burner for natural gas e and ll
Table of Contents

Advertisement

Troubleshooting
Fault codes with display on burner control unit
Detailed error codes for F FD
Detailed er-
Component/signal Cause of fault
ror code
30
Reset button
31
Fuel valve 2 feed-
back
32
Air pressure switch
1
34
Gas pressure
switch 1
35
Plug 41 demand T2 High switching se-
36
Plug 90 T8
37
Plug 90 T7 SK
38
Fuel valve 1 feed-
back
3A
Ignition feedback
3B
Air pressure switch
2
60
Hall signal fan feed-
back (RM-N)
Faults without fault display
Fault
Combustion faults due to
pulsation
Thermo-acoustics/
combustion noise
42
Programming unit faulty
Wiring
Incorrect return voltage
(e.g. DC voltage)
Actuator faulty
High switching se-
quence, switch flutters
External voltage
High switching se-
quence, switch flutters
External voltage
quence, switch flutters
External voltage
High switching se-
quence, switch flutters
External voltage
High switching se-
quence, switch flutters
External voltage
Incorrect return voltage
(e.g. DC voltage)
Actuator faulty
Incorrect return voltage
(e.g. DC voltage)
Actuator faulty
High switching se-
quence, switch flutters
External voltage
Fan speed too high. In-
correct fan or incorrect
coding card
Cause of fault
Excessive gas throughput
Insufficient or excessive air
Condensate backed up in flue
system
Flue outlet not installed cor-
rectly
Incorrect CO
settings; insuffi-
2
cient or excessive air
(cont.)
Measure
Replace programming unit.
Check wiring.
Remove plug from fuel valve 2, reset burner con-
trol unit and check error messages. If F Fd recurs,
replace burner control unit. Otherwise, replace
fuel valve 2.
Check flue gas path and combustion. Check set-
ting LDW1. Check burner gauze assembly for
contamination.
Check the gas supply. Check setting GDW1 and
gas train intake screen.
Check whether external voltage present.
Check on-site connection.
Check whether external voltage present.
Check on-site connection.
Check whether external voltage present.
Check on-site connection.
Remove plug from fuel valve 1, reset burner con-
trol unit and check error messages. If F Fd recurs,
replace burner control unit. Otherwise, replace
fuel valve 1.
Disconnect cable from ignition module, reset
burner control unit and check error messages. If
F Fd recurs, replace burner control unit. Other-
wise, replace ignition module.
Check flue gas path and reheating surfaces.
Check air pressure switch 2 setting.
Check the fan. Check coding card.
Measure
Adjust gas throughput in accordance with the rated
boiler heating output.
Check condensate drain.
Check flue outlet and flue system.
Adjust burner in accordance with the details on
page 16 onwards.