Commissioning, inspection, maintenance
Checking and cleaning the burner gauze assembly
A
B
Fig. 16
Checking the ignition electrodes and ionisation electrode
Ignition electrodes
±
31 3
Fig. 17
24
1. Check burner gauze assembly
2. If a component is visibly damaged, replace the
3. In the event of contamination, clean the burner
Ionisation electrode
±
4 2
Fig. 18
insulation block
for damage and contamination.
B
component.
Installation instructions "Replacing burner
components"
gauze assembly.
Clean the burner gauze assembly thoroughly with
compressed air then vacuum clean.
1. First from the combustion chamber side (against
the flow direction)
2. Then from the fan side (in flow direction)
Danger
Dust and soot particles affect breathing and can
cause damage to the lungs.
Wear a breathing mask when cleaning the
burner gauze assembly.
±
40.6 4
A
and thermal